Bgd36cf(g) top or rear exit vertical termination, 90° h, 90° v – Napoleon Fireplaces BGD36CFPTR User Manual

Page 14

Advertising
background image

14

W415-0661 / C / 02.20.08

REQUIRED
VERTICAL
RISE IN
FEET V

T

HORIZONTAL VENT RUN PLUS

OFFSET IN FEET H

T

The shaded area within the lines represents acceptable values
for H

T

and V

T

.

V

1

=5 ft

V

2

=10 ft

V

T

=V

1

+ V

2

= 5 + 10 = 15 ft

H

1

=3 ft

H

2

=2.5 ft

H

R

=H

1

+ H

2

= 3 + 2.5 = 5.5 ft

H

O

=.03 (three 90° elbows - 90°)

=.03(90 + 90 + 90 - 90) = 5.4 ft

H

T

=H

R

+ H

O

= 5.5 + 5.4 = 10.9 ft

H

T

+ V

T

= 10.9 + 15 = 25.9 ft

Formula 1:

H

T

< V

T

10.9 < 15

Formula 2:

H

T

+ V

T

< 40 feet

25.9

<

40

Since both formulas are met, this vent confi guration is ac-
ceptable.

when (H

T

) < (V

T

)

Simple venting confi guration (only two
90° elbows)

See graph to determine the required vertical rise V

T

for the required

horizontal run H

T

For vent confi gurations requiring more than zero 90° elbow (top exit)
or one 90° elbow (rear exit), the following formulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

Example 6:

90°

90°

90°

H

1

H

2

V

1

V

2

BGD36CF(G) TOP OR REAR EXIT VERTICAL TERMINATION

FIGURE 29

FIGURE 30

MAXIMUM
VERTICAL
R I S E I N
FEET

V

T

HORIZONTAL VENT RUN PLUS OFFSET IN

FEET H

T

The shaded area within the lines represents acceptable values
for H

T

and V

T

.

For vent confi gurations requiring more than two 90° elbows (top exit)
or one 90° elbow (rear exit), the following formulas apply:

Formula 1: H

T

< 3V

T

Formula 2: H

T

+ V

T

< 40 feet

Example 7:

See graph to determine

the required vertical rise V

T

for the required horizontal

run H

T

.

V

1

= 2 ft

V

2

= 1 ft

V

3

= 1.5 ft

V

T

= V

1

+ V

2

+

V

3

= 2 + 1 + 1.5 = 4.5 ft

H

1

= 6 ft

H

2

= 2 ft

H

R

= H

1

+ H

2

= 6 + 2 = 8 ft

H

O

= .03 (four 90° elbows - 90°)

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

H

T

= H

R

+ H

O

= 8 + 8.1 = 16.1 ft

H

T

+ V

T

= 16.1 + 4.5 = 20.6 ft

Formula 1:

H

T

< 3V

T

3V

T

= 3 x 4.5 = 13.5 ft

Since this formula is not met, this vent confi guration is unac-
ceptable.

Formula 2:

H

T

+ V

T

< 40 feet

20.6

<

40

H

1

H

2

V

3

V

1

90°

90°

90°

V

2

90°

when (H

T

) > (V

T

)

Simple venting confi gurations

FIGURE 31

FIGURE 32

Since only formula 2 is met, this vent confi guration is unacceptable
and a new fi replace location or vent confi guration will need to be
established to satisfy both formulas.