Bgd42cf minimum mantel and enclosure clearances – Napoleon Fireplaces BGD36CFPTR User Manual

Page 29

Advertising
background image

29

W415-0661 / C / 02.20.08

Combustible mantel clearance can vary according to the mantel depth. Figure 92. Use the graph to help evaluate the
clearance needed. These same requirements apply to any combustibles protruding on either side of the fi replace.

BGD42CF MINIMUM MANTEL AND ENCLOSURE CLEARANCES

This fi replace requires a minimum of 6 1/2" of cement board or
non-combustible equivalent above the top of the fi replace.

FIGURE 92b

FIGURE 92a

The fi replace requires a minimum enclosure height of 49“. For
temperature requirements, the enclosure space around and above
the fi replace must be left unobstructed.

* See Venting Section

FIGURE 92d

FIGURE 92c

Advertising
This manual is related to the following products: