Scanclk signal, Figure 4-12. scanclk signal timing, Scanclk signal -26 – National Instruments E Series User Manual

Page 62: Figure 4-12. scanclk signal timing -26

Advertising
background image

Chapter 4 Signal Connections

DAQCard E Series User Manual

4-26

National Instruments Corporation

SCANCLK Signal

SCANCLK is an output-only signal that generates a pulse with the

leading edge occurring approximately 50 to 100 ns after an A/D
conversion begins. The polarity of this output is software-selectable
but is typically configured so that a low-to-high leading edge can clock
external analog input multiplexers indicating when the input signal has
been sampled and can be removed. This signal has a 400 to 500 ns
pulse width and is software enabled. Figure 4-12

shows the timing for

the SCANCLK signal,

Figure 4-12.

SCANCLK Signal Timing

t

w

t

w

= 400 to 500 ns

t

d

= 50 to 100 ns

t

d

CONVERT*

SCANCLK

Advertising