Scxi-1341 and scxi-1344 installation, Table e-2, Scxi-1341 and scxi-1344 pin translations – National Instruments SCXI-1120 User Manual

Page 102

Advertising
background image

SCXI-1120 Cabling

Appendix E

SCXI-1120 User Manual

E-4

© National Instruments Corporation

Lab boards full access to the digital control lines and analog signals (except DTEMP), but the Lab
boards cannot scan channels in Multiplexed mode. Leave jumper W1 in position A on the
SCXI-1341 and SCXI-1344. The SCXI-1120 does not use jumper W1. Table E-2 lists the
SCXI-1341 and SCXI-1344 pin translations.

Note: If you are using the Lab-PC+, configure the board for single-ended inputs.

Table E-2. SCXI-1341 and SCXI-1344 Pin Translations

Lab Board Pin

Lab Board Signal

SCXI-1120 Pin

SCXI-1120 Signal

1

ACH0

3

MCH0+

2

ACH1

5

MCH1+

3

ACH2

7

MCH2+

4

ACH3

9

MCH3+

5

ACH4

11

MCH4+

6

ACH5

13

MCH5+

7

ACH6

15

MCH6+

8

ACH7

17

MCH7+

9

AIGND

1-2

AOGND

10

DAC0OUT

20

No Connect

11

AOGND

23

No Connect

12

DAC1OUT

21

No Connect

13, 50

DGND

24, 33

DIG GND

26

PB4

25

SERDATIN

27

PB5

27

DAQD*/A

28

PB6

29

SLOT0SEL*

29

PB7

37

SERCLK

31

PC1

26

SERDATOUT

32

PC2

28

No Connect

40

EXTCONV*

36

SCANCLK

43

OUTB1

46

No Connect

49

+5 V

34-35

No Connect

All other pins of the Lab board pinout are not sent to the SCXI-1120 rear signal connector.

SCXI-1341 and SCXI-1344 Installation

Follow these steps to install the SCXI-1341 or SCXI-1344:

1. Make sure that the computer and the SCXI chassis are turned off.

2. Install the SCXI module in the chassis.

3. Connect one end of the ribbon cable to the adapter board rear connector. This is the 50-pin

connector of the SCXI-1344 cable.

4. Plug the adapter board front connector to the module rear signal connector. Make sure a

corner of the adapter board enters the upper module guide of the chassis.

5. Screw the rear panel to the threaded strips in the rear of the chassis.

Advertising