CB 1200 Pellet Stove

R

R

Do not terminate vent in any enclosed or semi-enclosed

area such as a carport, garage, attic, crawl space, under a

sun deck or porch, narrow walkway or closely fenced area,

or any location that can build up a concentration of fumes

such as a stairwell, covered breezeway, etc.

CAUTION

Vent surfaces get HOT, can cause burns if

touched. Noncombustible shielding or guards

may be required.

WARNING

A. Chimney and Exhaust Connection

1.

Chimney & Connector: Use  or 4 inch (76-102mm)

diameter type "L" or "PL" venting system. It can be

vented vertically or horizontally.

2.

Mobile Home: Approved for all Listed pellet vent. If

using the  inch (76mm) vertical top vent adapter Kit

or the  to 6 inch (76-152mm) top vent offset adapter,

use Listed double wall flue connector. A Quadra-Fire

outside air kit must be used with manufactured home

installations.

.

Residential: The  inch (76mm) vertical top vent

adapter kit and the  to 6 inch (76-152mm) top vent

offset adapter are tested to use 24 gauge single wall flue

connector or Listed double wall flue connector to Class

A Listed metal chimneys, or masonry chimneys meeting

national and/or local codes for solid fuel appliances.

4.

INSTALL VENT AT CLEARANCES SPECIFIED BY THE

VENT MANUFACTURER.

5. Secure exhaust venting system to the appliance with at

least  screws. Also secure all connector pipe joints with

at least  screws through each joint.

NOTE: All pipe must be welded seam pipe whenever

possible. Seal pipe joints with high temperature silicone

(500°F [260°C] minimum rated only).

NOTE: If burning shelled field corn, you must use

approved venting specifically designed for corn. Follow

the instructions from the venting manufacturer.

Fire Hazard.
• Only LISTED venting components may be

used.
• NO OTHER vent components may be used.

Substitute or damaged vent components may

impair safe operation.

WARNING

B. Venting Termination Requirements

1

. Termination must exhaust above air inlet elevation. It is

recommended that at least 60 inches (1524mm) of verti-

cal pipe be installed when appliance is vented directly

through a wall. This will create a natural draft, which

will help prevent the possibility of smoke or odor venting

into the home during a power outage. It will also keep

exhaust from causing a nuisance or hazard by exposing

people or shrubs to high temperatures. The safest and

preferred venting method is to extend the vent vertically

through the roof.

2

. Distance from doors and opening windows, or gravity or

ventilation air inlets into building:
a. Not less than 48 inches (1219mm) below;

b. Not less than 48 inches (1219mm) horizontally

from;

c. Not less than 12 inches (05mm) above.

. Distance from permanently closed windows:

a. Not less than 12 inches (05mm) below, horizontally

from or above.

4

. Distance between bottom of termination and grade

should be 12 inches (05mm) minimum. This is con-

ditional upon plants in the area, and nature of grade

surface. The grade surface must be a non-combustible

material (i.e., rock, dirt). The grade surface must not be

lawn. Distance between bottom of termination and public

walkway should be 84 inches (214mm) minimum.

5

. Distance to combustible materials must be 24 inches

(610mm) minimum. This includes adjacent buildings,

fences, protruding parts of the structure, roof overhang,

plants and shrubs, etc.

6. Termination Cap Location (Home Electrical Service)

• Side-to-side clearance is to be the same as minimum

clearance to vinyl inside corners.

• Clearance of a termination cap below electrical service

shall be the same as minimum clearance to vinyl soffits.

• Clearance of a termination cap above electrical service

will be 12 inches (05mm) minimum.

• Location of the vent termination must not obstruct or

interfere with access to the electrical service.

4

Vent Information