CB 1200 Pellet Stove

*L Exception for Horizontal Installations:
USA INSTALLATIONS
: A non-combustible floor protec-

tion is recommended extending beneath the flue pipe

when installed with horizontal venting or under the top

vent adapter with vertical installation.
CANADA INSTALLATIONS: A non-combustible floor

protection extending beneath the flue pipe is

required

with horizontal venting or under the top vent adapter with

vertical installation.

Must extend 2 inches (51mm) beyond each

side of pipe (shaded area)

C. Hearth Pad Requirements (UL and ULC)

L*

K

K

M

Use a non-combustible floor protector, extending beneath

appliance and to the front, sides and rear as indicated.

Measure front distance “M” from the surface of the glass

door.

Hearth Pad Requirements

Inches Millimeters

K

Sides

2

51

L*

Back

2

51

M

Front

6

152

Alcove Installation

Inches Millimeters

Minimum Alcove Height

44

1117

Minimum Alcove Width

40-1/2

1029

Maximum Alcove Depth

6

915

Minimum Alcove Side Wall

6

152

Top of Unit to Combustibles

12-1/2

18