Warning, Cb 1200 pellet stove, D. pipe selection chart – Quadra-Fire CB1200-B User Manual

Page 11: C. equivalent feet of pipe

Advertising
background image

R

R

R

September 1, 2008

7014-082D

Page 11

CB 1200 Pellet Stove

Improper installation, adjustment, alteration, service or

maintenance can cause injury or property damage. Refer

to the owner’s information manual provided with this appli-

ance. For assistance or additional information consult a

qualified installer, service agency or your dealer.

WARNING

The chart will help you in determining proper

venting size according to the equivalent feet of

pipe calculated above and the altitude above sea

level of this installation.

Figure 11.2.

Locate the calculated equivalent feet of pipe on

the vertical left side of the chart. Move to the

right horizontally on the chart until you reach

your altitude above sea level.
If you fall below the diagonal line,  or 4 inch (76

to 102mm) pipe may be used. If it is anywhere

above the diagonal line, a 4 inch (102mm) diam-

eter pipe is required.
The chart reveals that a 90° elbow is 5 times as

restrictive to the flow of exhaust gases under

positive pressure as 1 foot of horizontal pipe, and

a foot of horizontal pipe is twice as restrictive as

a foot of vertical pipe.

D. Pipe Selection Chart

The table below can help you calculate the equivalent feet

of pipe which is a method used to determine pellet vent size.

Figure 11.1.

C. Equivalent Feet of Pipe

2 ft.

2 ft.

 ft.

2 ft.

Example of 3 Elbow-Rear Vent Termination Calculaton

Figure 11.1

Pellet Venting

Component

# of

Elbows

Feet of

Pipe

Multipled

By

Equivalent

Feet

Components

Equivalent Feet

90

o

Elbow or Tee



X

5

15

45

o

Elbow

X

3

Horizontal Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

Note: This is a generic example and is not

intended to represent any specific fuel type.

Fire Risk.
Do NOT pack insulation or other

combustibles between firestops.
• ALWAYS maintain specified clearances

around venting and firestop systems.

• Install firestops as specified.
Failure to keep insulation or other material

away from vent pipe may cause fire.

WARNING

3 in. or 4 in. (76mm or 102mm) Diameter Pipe

Equivalent Pipe

Length In Feet

ALTITUDE IN THOUSANDS OF FEET

0

20

30

1 2 3 4 5 6 7 8 9 10

4 in. (102mm) Diameter Pipe Only

10

Example 1

Example 2

Figure 11.2

Example 1: If the equivalent length of pipe is 2

feet with altitude of 8,000 feet you must use 4 inch

(102mm) diameter type “L” or “PL” vent.
Example 2: If the equivalent length of pipe is 12 feet

with altitude of 6,000 feet you may use  or 4 inch (76

to 102mm) diameter type “L” or “PL” vent