Termination locations, Warning, A. vent termination minimum clearances – Quadra-Fire QF130 User Manual

Page 19

Advertising
background image

19

Quadra-Fire • QFI30, QFI35 • 2227-900 Rev. H • 1/11

A. Vent Termination Minimum Clearances

Roof Pitch

H (Min.) Ft.

Flat to 6/12...........................................................1.0*

Over 6/12 to 7/12 .................................................1.25*

Over 7/12 to 8/12 .................................................1.5*

Over 8/12 to 9/12 .................................................2.0*

Over 9/12 to 10/12 ...............................................2.5

Over 10/12 to 11/12 .............................................3.25

Over 11/12 to 12/12 .............................................4.0

Over 12/12 to 14/12 .............................................5.0

Over 14/12 to 16/12 .............................................6.0

Over 16/12 to 18/12 .............................................7.0

Over 18/12 to 20/12 .............................................7.5

Over 20/12 to 21/12 .............................................8.0

Figure 6.1 Minimum Height From Roof To Lowest Discharge

Opening

* 3 foot minimum in snow regions

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT

TERMINATION CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

6

Termination Locations

Fire Risk.
Maintain vent clearance to combustibles as

specifi ed.

DO NOT pack air space with insulation or

other materials.

Failure to keep insulation or other materials

away from vent pipe may cause fi re.

WARNING

Figure 6.2 Staggered Termination Caps

Gas, Wood or Fuel Oil

Termination Cap

B

Gas

Termination

Cap **

A *

*

If using decorative cap cover(s), this distance may need to be

increased. Refer to the installation instructions supplied with the

decorative cap cover.

**

A

B

6 in. (minimum) up to 20 in.

152 mm/508 mm

18 in. minimum

457 mm

20 in. and over

0 in. minimum

In a staggered installation with both gas and wood or fuel oil

terminations, the wood or fuel oil termination cap must be

higher than the gas termination cap