F. installing adaptor and termination cap, Masonry factory built wood burning – Quadra-Fire QF130 User Manual

Page 23

Advertising
background image

23

Quadra-Fire • QFI30, QFI35 • 2227-900 Rev. H • 1/11

F. Installing Adaptor and Termination Cap

For installation of termination cap see minimum vent

heights for various pitched roofs (see Figure 8.4) .
To install adaptor see Figure 8.5.

Roof Pitch H (Min.) Ft.
Flat to 6/12....................1.0*
Over 6/12 to 7/12 ........1.25*
Over 7/12 to 8/12 ..........1.5*
Over 8/12 to 9/12 ..........2.0*
Over 9/12 to 10/12 ........2.5*
Over 10/12 to 11/12 ..... 3.25

Figure 8.4 Minimum Height from Roof to Lowest Discharge

Opening

* 3 foot minimum in snow regions

Roof Pitch H (Min.) Ft.
Over 11/12 to 12/12 ....... 4.0
Over 12/12 to 14/12 ....... 5.0
Over 14/12 to 16/12 ....... 6.0
Over 16/12 to 18/12 ....... 7.0
Over 18/12 to 20/12 ....... 7.5
Over 20/12 to 21/12 ....... 8.0

CLASS A PIPE

Figure 8.5

Figure 8.6

To prevent odors and cold drafts, the chimney must be sealed around the vent

with non-combustible blanket insulation or fi eld fabricated metal plates.

Masonry

Factory Built

Wood Burning

Remove 18 inch x 18 inch fl ashing on cap by removing 3

screws. Connect both the LINK-ZC-ADPB to Class A Pipe

and the termination cap to the LINK-ZC-ADPB with the

self tapping screws provided.

OPTIONAL LINK-ZC-ADPB

FOR USE WITH CLASS A

WOODBURNING PIPE

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT

TERMINATION CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

CAUTION! Risk of Cuts/Abrasions/Flying Debris.

Wear protective gloves and safety glasses during instal-

lation. Sheet metal edges are sharp.
Damper Flashing Kit (Optional)
For use with LINK-DV30B or LINK-DV4-30B Liner Kit.
Note: Damper may have to be removed to use this kit.
• Run fl ex liners through 3 in. holes in damper fl ashing.
• Attach damper fl ashing to fi rebox roof with self tapping

screws included in kit.

Note: The LINK-DV4-30B

system REQUIRES this insulation.

EXHAUST

AIR

VENT PIPE

TERMINATION

CAP

LINK-DV30B

Installation

LINK-DV4-30B

Installation

INLET AIR

VENT PIPE

WARNING:

DO NOT BLOCK

THIS PIPE END!

INLET AIR

VENT PIPE

EXHAUST

AIR

VENT PIPE

Note: Untwist the

pipe while extend-

ing it, to achieve full

30’ length.

OR