ACCESSORY AND REFRIGERANT

Accessory and Installation Parts

Refrigerant Piping

• Piping kit used for the conventional refrigerant cannot

be used.

• Use copper pipe with 0.8 mm or more thickness for

Ø9.5 mm.

Use copper pipe with 1.0 mm or more thickness for
Ø15.9 mm.

• Flare nut and flare works are also different from those

of the conventional refrigerant. Take out the flare nut
attached to the main unit of the air conditioner, and
use it.

3

SELECTION OF INSTALLATION

Before installation

Be careful to the following items before installation.

Length of refrigerant pipe

Length of refrigerant pipe

connected to

indoor/outdoor unit

20m or shorter

*

21m to 50m

Item

Addition of refrigerant is
unnecessary at the local site.

<Addition of refrigerant>
Add 40g of refrigerant for every
1m of pipe which exceeds 20m.

* Caution at addition of refrigerant

When the total length of refrigerant pipe exceeds
20m, add 40g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 1200g.)

Charge the refrigerant accurately. Overcharge may
cause a serious trouble of compressor.

Air purge

• For air purge, use a vacuum pump.

• Do not use refrigerant charged in the outdoor unit for

air purge. (The refrigerant for air purge is not con-
tained in the outdoor unit.)

Electrical cabling

• Be sure to fix the power cables and indoor/outdoor

connecting cables with clamps so that they do not
contact with the cabinet, etc.