External sounders – Vista Ademco N7227V5 User Manual

Page 31

Advertising
background image

8–1

S E C T I O N 8

External Sounders

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

In This Section

Compatible Sounders

NFPA Requirements

Sounder Connections and Power

Sounder Supervision

Testing the Sounder

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Compatible Sounders

ADEMCO AB-12M 10” Motorized
Bell & Box

Motor bell & box. UL Grade A. 100mA current draw.

ADEMCO 1011BE12M 10”
Motorized Bell & Box

Motor bell & box. UL Listed. 100mA current draw.

ADEMCO 702
Outdoor Siren

Self-contained 6–12 volt siren (driver built-in) and
weatherproof for outdoor use. Can be wired for either a
steady or warble sound. 117dB @ 10 feet. 1500mA current
draw.

ADEMCO 719
2-Channel Siren

Self-contained 6–12-volt siren (driver built in). Steady or
warble sound. 109dB @ 10 feet. 550mA current draw.

ADEMCO 747
Indoor Siren

Self-contained 6–15 volt siren (driver built-in) for indoor
wall mount. 747F available for flush mounting. 105dB @ 10
feet. 400mA current draw.

ADEMCO 747UL
Indoor Siren

Self-contained 6–15 volt siren (driver built-in) for indoor
wall mount. UL Listed. 85dB @ 10 feet. 320mA current
draw.

ADEMCO 744

Siren Driver

6 jumper-selected sound outputs. Rated at 119dB with use
of an 8-ohm 30 watt speaker. 1.3 amps current draw.

ADEMCO 745X3
Voice Siren Driver

12-volt voice siren driver with English, Spanish, and
French voice messages. Separate messages for fire and
burglary. Use with 8-ohm speaker. UL Listed. 1100mA
current draw. NOTE: Requires special power wiring, using
additional components.

ADEMCO 705–820,
5-inch Round Speaker

20-watt, 8-ohm indoor or outdoor speaker. Requires a
driver.

ADEMCO 713 Speaker

40-watt, 8-ohm, indoor/outdoor speaker. Requires a driver.

System Sensor PA400B
(beige)/PA400R (red)

Indoor Piezo Sounder

Indoor piezo sounder (red or beige), rated at 90 dB @ 10
feet.

UL

For UL installations, use only UL Listed sounding devices mounted indoors.

NFPA Requirements

The VISTA-10SE complies with NFPA requirements for temporal pulse sounding of fire
notification appliances.

Temporal pulse sounding for a fire alarm consists of the following:

3 pulses – pause – 3 pulses – pause – 3 pulses . . .

Advertising
This manual is related to the following products: