Final power-up – Vista Ademco N7227V5 User Manual

Page 37

Advertising
background image

11–1

S E C T I O N 1 1

Final Power-Up

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

In This Section

Earth Ground Connections

Wiring the AC Transformer

AC Power-Up

Calculating the Battery Size Needed

Connecting the Backup Battery

Battery Tests

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Earth Ground Connections

The designated earth ground terminal (21) must be terminated in a good earth ground for
the lightning transient protective devices in this product to be effective.

The following are examples of good earth grounds available at most installations:

Metal Cold Water Pipe:

Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which
the ground lead is electrically connected and secured.

AC Power Outlet Ground:

Available from 3-prong, 120VAC, power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL-Listed
Ideal Model 61–035, or equivalent, available at most electrical supply stores.

Wiring the AC Transformer

1321 Transformer

Wire the 1321 Transformer to terminals 1 and 2 on the control board. See wiring table below
for wire gauge to use.

WIRING TABLE

Distance of Transformer
From the Control Panel

Wire Gauge

to Use

Up to 50 feet

# 20

50 – 100 feet

# 18

100 – 250 feet

# 16

Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire.

Do not plug the transformer into the AC outlet until you are instructed to do so later in the

manual.