Installation

2–14

975-0131-01-01

AC/DC Disconnect Switch

The wiring box includes a PV/Utility disconnect switch that switches both AC and
DC at the same time. If the inverter is to be installed without the integral Xantrex
Wiring Box with Disconnect (Xantrex Part # 100-0243-01-01), separate approved
AC and DC disconnects may be required by local authorities having jurisdiction.

Ground Fault Fuse

There is a 600 volt 1-Amp ground fault protection fuse (Littelfuse KLKD 1 or
equivalent) in the GT Inverter.

Other Materials Needed

Mounting support material, such as plywood or poles

Conduit for wire runs and appropriate fittings/bushings

Wood screws and anchors for screws, depending on mounting surface.

Equipment Needed

Wire cutters/wire crimpers/wire strippers

Assorted screwdrivers, drill, etc.

Level

Digital Voltmeter

Frequency counter (optional, for troubleshooting).

WARNING: Shock hazard

The 600 volt DC/AC disconnect in the wiring box meets NEC Article 690. It is a
non-serviceable component and shall remain in place. Removal can expose energized
conductors.

WARNING: Shock hazard

Do not attempt to service the ground fault fuse yourself. This should only be done by
qualified service personnel.