Warning: shock hazard, Warning: personal injury, Warning: explosion hazard – Xantrex Technology GT3.0 User Manual

Page 47

Advertising
background image

Mounting the Inverter

975-0131-01-01

2–19

Surfaces for Mounting

The GT Inverter

weighs approximately 20 kg (45 lbs). The supporting surface

must be strong enough to handle 75 kg (160 lb). If the supporting surface is not
strong enough to handle that weight, then supporting material such as a sheet of
plywood can be used to enhance the strength of the mounting surface.

The GT Inverter can be mounted to a vertical surface such as wallboard, wood
siding, concrete wall or pole assembly.

Mounting on poles
or rails

See “Mounting on Poles or Rails” on page 2–20. Ensure the bottom of the unit
is a minimum of 100 cm (39 inches) from the ground if mounted outdoors.

Mounting to
wallboard with
support

Installation onto wallboard requires either the use of a supporting material
such as plywood or securing the mounting screws to supporting wall studs.
Use at least two screws and anchors to secure the unit to the supporting
material.

Mounting to siding
using wall studs

If mounting to exterior siding using a wall stud for support, the plywood
backing will not be needed. Use at least two lag screws to secure the unit to
the supporting material. Ensure the screws enter the stud at least 4 cm
(1.5 inches) to adequately support the weight of the unit. See “Mounting on
Wallboard, Siding or Concrete” on page 2–21.

Mounting to
concrete surface

If mounting the unit on a concrete surface using anchors with no supporting
material, use four screws and anchors, instead of two, to adequately secure the
unit and distribute the weight.

WARNING: Shock hazard

Before drilling holes to mount the GT Inverter, ensure there are no electrical wires or
plumbing in this area.

WARNING: Personal injury

The GT Inverter weighs approximately 20 kg (45 lbs). Always use proper lifting
techniques during installation to prevent personal injury.

WARNING: Explosion hazard

Do not store combustible or flammable materials anywhere near the inverter.

Important:

Local codes may impose additional mounting requirements in earthquake

or other high-risk areas.

Important:

Other than the mounting bracket, no mounting hardware is supplied with

the GT Inverter.