F08 set peukert’s exponent, F09 set low battery discharge floor – Xantrex Technology Link 1000 User Manual

Page 40

Advertising
background image

About Link 1000 Settings

32

F08 Set Peukert’s Exponent

Default:

1.25 for liquid lead-acid batteries. (Battery Type set

to Type 0.)

The Peukert exponent refers to the “shrink rate” of your
battery bank. The more rapidly you discharge the batteries,
the more their effective size shrinks. For example, a battery
that can supply 200Ah when discharged over twenty hours
may only provide 95Ah if discharged in one hour.

When you select Battery Type (see

“Changing the Battery

Type Setting” on page 23

and

“F10 Select Battery Type” on

page 33

), the Link 1000 automatically sets an appropriate

Peukert exponent. When the Battery Type is gel or AGM
(Type 1, 2, or 3), a default exponent of 1.11 is used.

If your battery manufacturer has given you another value,
you can enter it. Otherwise, leave the default value.

F09 Set Low Battery Discharge Floor

Default:

100%

Range:

50%–100% in 5% increments

The Link 1000 lets you set the discharge floor that it uses for
calculations. The factory-set discharge floor is 100% of Ah
capacity, corrected for high discharge rates. If you set the
discharge floor to 100%, the Time Remaining display

reports the time that remains until you have a dead battery.
We recommend that you begin charging when two yellow
battery status LEDs are on in order to conform to the “Mid
Capacity Rule” (see

page 39

).

Note: If you discharge below the discharge floor, and then
partially charge but remain below the discharge floor, the Time
Remaining display will continue to read zero. The Time Remaining
display will not show meaningful readings until you have recharged
above the discharge floor you have set.