5 technical data – VEGA VEGACOM 557 VEGA ASCII protocol User Manual

Page 10

Advertising
background image

10

VEGACOM 557 VEGA ASCII

1.5 Technical data

Power supply

Supply voltage

U

nom

= 24 V AC (20 … 53 V), 50/60 Hz or
= 24 V DC (20 … 72 V)

Power consumption

approx. 6 VA

Fuse

1 A, slow-blow

Electrical connection

Component

multiple plug acc. to DIN 41 612, series F
48 pole (d, b, z) with coding holes

Module in carrier
BGT 596 or BGT LOG 571

suitable multipoint connector acc. to DIN 41 612
with connection via standard technologies

Housing type 505

via screw terminals max. 1 x 1.5 mm

2

Indicating elements

LED on front panel

green "BA“:

VEGA ASCII active

red:

failure, freeze mode

green "on“:

operating mode

Meas. data input DISBUS

Data transmission

DISBUS (digital data transmission)

Connection cable

2-wire standard cable (shielded)

Cable length

max. 1000 m

Measuring data input LOGBUS

Data transmission

LOGBUS (digital data transmission)

Connection cable

connection via BUS-plug

PC interface

Interface standard

RS 232C

Cable length

max. 15 m

Transmission rate in baud

300, 600, 1200, 2400, 4800, 9600

9600

9600

9600

9600, 19200, 38400

Transmission format

8 data bits, 1 stop bit, no parity or even
parity

Plug on front panel

SUB-D-plug connector, 9 pole, pins

Modbus interfaces

Interfaces

RS 232

RS 422

RS 485

TTY

Cable length

15 m

1200 m

1200 m

1000 m

Connection cable

3-wire

5-wire

3-wire

4-wire

twisted in pairs, shielded

Transmission mode

serially asynchronous, half-duplex

Transmission rate

300; 600; 1200; 2400; 4800; 9600; 19200;
38400 baud

Galvanic separation

up to 0.5 kV

Product description

Advertising