46

VEGACOM 557 VEGA ASCII

5 Setup

5.1 Setup check list:

Proceed with the setup of VEGACOM 557
with VEGA ASCII as follows:

I. Check hardware requirements:

• VEGA ASCII-compatible Master compo-

nent
(Modus: RTU or ASCII)

• Check interface type (RS 232, RS 485,

RS 422 or TTY)

• VEGACOM 557 version "VEGA ASCII“

II. Carry out adjustments on VEGACOM
557 (DIL switch on additional board):

• Set resolution for VEGA ASCII
• Set value arrangement for VEGA ASCII
• Activate interface type
• Set parameter for interface
• Set VEGA ASCII address

III. Provide VEGA ASCII connection and
check communication:

• In case of correct communication, the

green LED marked "BA“ lights on VEGA-
COM 557.

Setup

5.2 Communication structure

Within the data communication between
VEGACOM 557 and the connected process-
ing system, the following functions are sup-
ported:

- Mode (VEGACOM 557 is slave)

VEGACOM 557 does not transmit data
without request. The Master has to request
all required data.

- Instrument address (default value # 1)

By using a bus-compatible interface (e.g.
RS 485) the operation of up to 9 instru-
ments on one interface is possible.

- Presentation:

All telegrams use ASCII characters and are
therefore readable as plain text.

- Time-based image:

There are no time periods required for
transmission.

- Value range (low resolution)

Independent of the actual position of the
decimal point, the value to be transferred is
provided with a decimal point at the penul-
timate position.

- Value range (high resolution)

The value to be transmitted is always
transferred without decimal point.

The decimal point as well as the unit of meas-
urement of the DCS value are not transferred
by VEGACOM 557!

This information must be completed by the
user in the software of the process data
processing.