VEGA VEGACOM 557 VEGA ASCII protocol User Manual

Page 41

Advertising
background image

VEGACOM 557 VEGA ASCII

41

High resolution = switch 2.2 = ON

The same enquiry can also be carried out with high resolution. The enquiry to VEGACOM 557
remains the same, however in the answer, more characters are used for the presentation of
the measured value.

Answer of VEGACOM 557

Telegram from processing system to VEGACOM 557

Identifier: 1 character, "%“
T1: 1 character ",“ (comma)
T2: 1 character "L“
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 11 characters

Data image in VEGACOM 557

DCS

DCS

End

S1

Addr

T1

no.

S2

value2

identification

No. of bytes

1

1

1

3

1

7

2

Range (ASCII)

=

0..9

,

001..255

#

DCS value

or fault

%CR

Example

=

2

,

001

#

-000673

%CR

n (n= stated number) repetitions

Start character: S1 = 1 character "=“
Address: Addr = 1 characters VEGACOM 557 address
Separating character: S2 = 1 character ",“ (comma)
Start character: S3 = 1 character "#“
Total length of the telegram: 16 characters

6 digit figure

"-“ with negative values
" " with positive values

valid meas. value

‘FAULT ’

Fault

1 2 3 4 5 6 7

1 2 3 4 5 6 7

DCS

DCS

End

Identifier Address T1

number

T1

number

identification

No. of bytes

1

1

1

3

1

3

1

Range (ASCII)

%

0..9

,

001..255

L

001..255

CR

Example

%

2

,

001

L

2

CR