5 enquiry as range with low resolution – VEGA VEGACOM 557 VEGA ASCII protocol User Manual

Page 34

Advertising
background image

34

VEGACOM 557 VEGA ASCII

4.5 Enquiry as range with low resolution

Low resolution = switch 2.2 = OFF

This telegram reads in a DCS value from VEGACOM 557. Depending on the position of the
switch 2.1, the DCS values are arranged differently. The assignment of the DCS numbers to
the VEGAMET addresses is stated in supplement A.

Answer of VEGACOM 557

Start character: S1 = 1 character "=“
Start character: S2 = 1 character "#“
Total length of the telegram: 12 or 13 characters

Telegram from processing system to VEGACOM 557

n (n= stated number) repetitions

1 2 3 4 5 6

3 positions in front of the decimal point
1 decimal point
1 position after the decimal point
"-“ with negative values
" " with positive values

valid measured value

1 2 3 4 5

‘FAULT’

Fault

Identifier: 1 character, "%“
T1 : Separating character = 1 character "L“
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 9 characters

Data image in VEGACOM 557

DCS

DCS

End

S1

no.

S2

value2

identification

No. of bytes

1

3

1

5-6

2

Range (ASCII)

=

001..255

#

DCS value or

fault

%CR

Example

=

001

#

-067.3

%CR

DCS

End

Identifier

number

T1

Number identification

No. of bytes

1

3

1

3

1

Range (ASCII)

%

001..255

L

001..255

CR

Example

%

001

L

001

CR

Advertising