VEGA VEGACOM 557 VEGA ASCII protocol User Manual

Page 33

Advertising
background image

VEGACOM 557 VEGA ASCII

33

Data image in VEGACOM 557

High resolution = switch 2.2 = ON

The same enquiry can also be carried out with high resolution. The enquiry to VEGACOM 557
remains the same, however in the answer, more characters are used for the presentation of
the measured value.

Answer of VEGACOM 557

Start character: S1 = 1 character "=“
Start character: S2 = 1 character "#“
Total length of the telegram: 13 characters

Telegram from processing system to VEGACOM 557

Identifier: 1 character, "%“
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 5 characters

One repetition

6 digit figure

"-“ with negative values
" " with positive values

valid measured value

‘FAULT ’

Fault

1 2 3 4 5 6 7

1 2 3 4 5 6 7

DCS

DCS

End

S1

no.

S2

value2

identification

No. of bytes

1

3

1

7

2

Range (ASCII)

=

001..255

#

DCS value or

fault

%CR

Example

=

001

#

-000673

%CR

DCS

End

Identifier

number

identification

No. of bytes

1

3

1

Range (ASCII)

%

001..255

CR

Example

%

001

CR

Advertising