11 enquiry for the software version, 12 error information from vegacom 557 – VEGA VEGACOM 557 VEGA ASCII protocol User Manual

Page 44

Advertising
background image

44

VEGACOM 557 VEGA ASCII

4.12

Error information from VEGACOM 557

If an enquiry of VEGACOM 557 was not understood correctly or the transmission of the en-
quiry was faulty, VEGACOM sends an error information.

Error text

Meaning

"ERROR 5“

- Identifier not recognised
- Telegram incomplete
- VEGAMET address not valid

"ERROR 6“

Telegram cannot be evaluated

4.11

Enquiry for the software version

With this enquiry, the software version in VEGACOM 557 can be determined.

Answer of VEGACOM 557

Start character: S1 = 1 character "=“
Address: Addr = 1 character VEGACOM 557 address
Reserve: 2 characters here "00“
Answer: 17 characters text
Total length of the telegram: 23 characters

Telegram from processing system to VEGACOM 557

Identifier: 1 character, "v“ ("V“)
Request: 13 characters " READ VERSION“ (in front of READ and in front of VERSION with 1 blank character)
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 18 characters

Data image in VEGACOM 557

Address

End

Identifier VEGACOM Reserve

Enquiry

identification

No. of bytes

1

1

2

17

2

Range (ASCII)

=

0..9

00

Answer text

CRLF

Example

=

2

00

VEGACOM557 V2.17

CRLF

Address

End

Identifier VEGACOM Reserve

Enquiry

identification

No. of bytes

1

1

2

13

1

Range (ASCII)

%

0..9

00

READ VERSION

CR

Example

%

2

00

READ VERSION

CR

Advertising