VEGACOM 557 VEGA ASCII

21

Bottom view of VEGACOM 557

Possible settings of DIL switch block 1 on the addi-
tional board

Switch settings on VEGACOM 557

3.2 Adjustment of the VEGA ASCII

interface

Three 8-pole DIL switch blocks as well as two
hook switches for configuration of the VEGA
ASCII interface to the DCS or the PLC are
located on the additional board.

The following adjustments for the VEGA
ASCII are made through these DIL-switch
blocks:

Switch 1
- selection of the interface type
- activation of the bus termination
- selection of the protocol

Switch 2
- selection of the baud rate
- number of data bits
- mode for parity bit
- resolution
- definition of the measured value image

Switch 3
- VEGA ASCII address of VEGACOM 557

Note:

When holding VEGACOM 557 for adjustment
of the DIL-switches 1 to 3 (shown in illustra-
tion 2.10), the following switch representation
can be applied directly.

Note:

When selecting the interfaces TTY and
RS 232, the hook switches must also be set
to the respective position.

Activation of the bus termination on RS 485 is
necessary when VEGACOM 557 is the last
participant. General rule: The first and the last
bus participant must be operated with bus
termination activated.

When using interface RS 422, the bus termi-
nation must always be activated on VEGA-
COM 557.

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

Multiple plug

Basic board

DIL switch
basic board

Front
plate

DIL switch blocks

additional board

Additional
board

2 1

1

2 3

Hook switches
additional
board

DIL switch block 1
(additional board)

Selection of the interface type

Bus termination for RS 485/
422

Protocol selection

TTY

RS 422, RS 485

RS 232

On

Off

VEGA ASCII

Factory setting

1

2

3

4

5

6

7

8

ON