PNEG-1820 CE Compliant Top Dry Series 2000 Autoflow

13

5. Fuel Installation

Fuel Supply

The dryer requires a suitable fuel supply. Refer to fuel specifications

Table on Page 11

for fuel

flow requirements.

Liquid LPG

Dryers with internal vaporizers require LPG in liquid form.

Vapor LPG

Dryers without internal vaporizers require LPG in vapor form.

LPG tanks must have adequate vaporizing capacity to supply the maximum fuel flow given in
fuel specifications

Table on Page 11

. Alternatively and external vaporizer may be used.

For twin fan units, double the fuel flow.

Primary pressure regulation is required at the tank, including over pressure protection.

Supply pressure at the dryer should be 1.5 bar-2.0 bar (150 kPa-200 kPa).

Natural Gas

Natural gas dryers require a supply capable of the maximum flow given in fuel specifications

Table on Page 11

.

For twin fan units, double the flow.

Minimum supply pressure at the dryer must be 750 mBar (75 kPa).

Primary pressure regulation should include over pressure protection.