Control panel setup, Control panel calibration – Grain Systems Bucket Elevtors, Conveyors, Series II Sweeps PNEG-1366 User Manual

Page 25

Advertising
background image

5. Assembly

PNEG-1366 12" and 16" Series II Sweep Quick Disconnect Control Box Kit

25

Control Panel Setup

NOTE: The control panel may have to be reprogrammed for peak performance after being moved to a

different bin.

The bin must have grain in it to be able to properly fine tune the control panel.

If the meter looks like this:

Figure 5I

Control Panel Calibration

Observe the tractor drive motor nameplate and the auger drive motor nameplate.

Record the full load amp (FLA) value for the specific voltage on each motor.

Auger drive motor full load amps: ____
Tractor drive motor full load amps: ____

Switch the disconnect switch on the panel to OFF (not ON).

Unlock and open the control panel.

Adjust the FLA dial screw on the tractor drive motor contactor (M1) and the auger drive motor
contactor (M2) so that the indicator arrowhead is set slightly higher than the full load amp value listed
on the nameplates.

Tractor drive motor contactor (M1) FLA adjustment dial: ____
Auger drive motor (M2) FLA adjustment dial value: ____

Close and lock the control panel.

Switch the disconnect switch on the panel to ON (not OFF).

Advertising