Grain Systems Bucket Elevtors, Conveyors, Series II Sweeps PNEG-1366 User Manual

Page 28

Advertising
background image

5. Assembly

28

PNEG-1366 12" and 16" Series II Sweep Quick Disconnect Control Box Kit

HYS1 should be displayed on the unit.

For this control panel hysteresis (HYS1) is measured as the different between 90% of full load amps and
110% of no load amps.

90% of full load amps: ____ minus 110% of no load amps: ____

Press

or

on the display unit until the correct value is shown.

Press OK.

ERR1 should be displayed on the unit.

Press

or

on the display unit until DEAC is shown (not HOLD, ACTI, or NONE).

Press OK.

ON.DE should be displayed on the unit.

Press

or

on the display unit until 0 is shown.

Press OK.

OF.DE should be displayed on the unit.

Press

or

on the display unit until 20 is shown.

Press OK.

REL2 should be displayed on the unit.

Press

or

on the display unit until OFF is shown (not SET or SKIP).

Press OK.

E.PAS should be displayed on the unit.

Press

or

on the display unit until NO is shown.

Press OK.

This function will allow the values that were entered to be locked.

NOTE: Using a password will stop access to the menu and parameters. There are two (2) levels of

password protection. Passwords between 0000 and 4999 allow access to the fast set point
adjustment and relay test. (Using this password stops access to all other parts of the menu.)
Passwords between 5000 and 9999 stop access to all parts of the menu, fast set point adjustment
and relay test. (Current set point is still shown.) By using the master password 2008, all
configuration menus are available.

Advertising