Chapter 7: power supply – Grain Systems PNEG-1891 User Manual

Page 48

Advertising
background image

Chapter 7: Power Supply

Table 7-1 Specifications for the electrical load on a portable dryer (cont'd.)

Dryer

model

Voltage

Motor

HP

Fuel Load

Amps

Maximum amps

with auxiliaries

Minimum

amps

Recommended

service in amps

Branch breaker

in amps

1218
2125

1 PH 230V

Load auger

5

26

286

178

400

100

Unload auger

5

26

100

Top Fan

10 to 17

78

100

Bottom Fan

10 to 12

48

100

(2) Auxiliary

(2) 7.5

62

*

3 PH 220V

Load auger

5

13.2

183

98.4

225

60

Unload auger

5

13.2

60

Top Fan

15

39

60

Bottom Fan

10 to 12

33

60

(2) Auxiliary

(2) 10

52

*

3 PH 440V

Load auger

5

6.6

96

49.2

150

60

Unload auger

5

6.6

60

Top Fan

15

19.5

60

Bottom Fan

10 to 12

16.5

60

(2) Auxiliary

(2) 10

26

*

1220
2130

1 PH 230V

Load auger

7.5

31

298

188

400

100

Unload auger

7.5

31

100

Top Fan

10 to 17

78

100

Bottom Fan

10 to 12

48

100

(2) Auxiliary

(2) 7.5

62

*

3 PH 220V

Load auger

7.5

20

229

112

300

90

Unload auger

7.5

20

90

Top Fan

15

39

60

Bottom Fan

10 to12

33

60

(2) Auxiliary

(2) 15

78

*

3 PH 440V

Load auger

7.5

10

123

59

200

60

Unload auger

7.5

10

60

Top Fan

15

19.5

60

Bottom Fan

10 to 12

16.5

60

(2) Auxiliary

(2) 15

39

*

1222
2132

3 PH 220V

Load auger

7.5

20

241

123

350

90

Unload auger

7.5

20

90

Top Fan

20

50

90

Bottom Fan

10 to 12

33

60

(2) Auxiliary

(2) 15

78

*

3 PH 440V

Load auger

7.5

10

129

64.5

200

60

Unload auger

7.5

10

60

Top Fan

20

25

60

Bottom Fan

10 to 12

16.5

60

(2) Auxiliary

(2) 15

39

*

48

Pneg-1891 Portable Dryers