Note (acc. to DIN VDE 0100/11.85, T 520, Sect. 528.11):

•

•

Cables or lines that are insulated for the maximum operating

voltage must be used, or each conductor of a multi-wire cable/
line must be insulated for the next voltage appearing in the
cable/line.

•

•

When laying conductor lines in electrical installation pipes or

ducts only the conductors of a main power circuit including the
associated auxiliary power circuit may be laid together

•

•

Several main power circuits including the associated auxiliary

power circuits can also be combined in a single cable or line

•

Cables and terminals approved for use the mains voltage (230 V)
must be used for the installation

•

The installation must be carried out in such a way that when the
supply voltage is switched off, all signal and control cables are also
switched off at the same time

•

All components of the main power and control power circuits must
be designed for 250 V working voltage to ground

•

All the luminaires must be wired with H05 cables provided U

OUT

does not exceed 430 V

eff,

and also be subjected to an insulation

test (in accordance with VDE) in conjunction with OSRAM DALI/
DIM ECGs. OSRAM QUICKTRONIC DALI/DIM ECGs do not ex-
ceed 430 V

eff

even for T5-Ø 16 mm HE and HO florescent lamps.