What insulation is required for the DALI control line?

The DALI control line must be approved for mains voltage (as in the

case of the 1…10 V interface).

•

Can existing 1…10 V control lines be used?

Yes, provided they are rated for mains voltage.

•

How long can a control line be?

A maximum of 300 m between the controller and the furthest con-

nected DALI unit.

•

Can control and power cables be laid together?

Yes, a 5 x 1.5 mm

2

NYM cable can be used, for example.

•

What line cross section must the control line have?

Up to 100 m: min. 0.5 mm

2

/from 100 m to 150 m: 1.0 mm

2

/from

150 m: 1.5 mm

2

.

•

Can any company develop a DALI controller or DALI ECG?

Yes, there are no restrictions except that the DALI logo

may only be used by members of the DALI Activity Group.
See also http://www.dali-ag.org/.

•

What happens if I use DALI ECGs from different manufactur-
ers in the same system?

The controllers are DALI-compatible if they carry the DALI logo. It is

important to note, however, as in 1…10 V technology, ECGs from
different manufacturers can result in different filament preheating
times and different lamp starting times.

•

Can controllers from different manufacturers be combined?

No, DALI ECGs are interchangeable, but the control components

cannot normally be combined.

•

Is it possible to limit the maximum and minimum luminous
flux?

Yes, these values can be changed/limited with the appropriate

controller in the ECG.