Note:

•

Only use switches without control lamp and with 230 V normally-
closed contact as the permanent current through the glow lamp
can lead to malfunctions

•

TouchDIM is not part of the DALI standard (IEC 62386), but rather
an additional OSRAM function

3.2.2 Operating parameters for TouchDIM

To operate the TouchDIM, AC voltages of 10…230 V (RMS) at
a frequency of 46…66 Hz can be used – there is no DC voltage
allowed.

3.2.3 Compensation of interferences

A control transformer which complies to the following figures and val-
ues must be used with a total line length from the switch to the ECG of
25 m to 100 m in order to prevent interference (e.g. through capacitive
induction):

Primary 230 V/Secondary 12 V, transformer rating required: 25 mW
per connected ECG (i.e. 150 mW with 6 ECGs 2 mA control current
per ECG)

DA

DA

~
~

L

N

PE

DALI ECG

Installation line

Button

12 V Transformer

Min. power: 25 mW x no. of ECGs

Figure

17: Control transformer for compensation close to the ECG

(e. g. in a luminaire)

DA

DA

~
~

L

N

PE

DALI ECG

Min. power: 25 mW x no. of ECGs

12 V Transformer

Button

Installation line

Figure 18: Control transformer close to the switch (e.g. in the subdis-
tributor or in a flush-mounted socket)