OSRAM QUICKTRONIC INTELLIGENT DIM CFL User Manual

Page 75

Advertising
background image

74

•

Can a DALI ECG belong to more than one group at the same
time?

Yes. Each DALI controller can belong to up to 16 groups.

•

Where are the data for the group assignments and light
scene values stored?

They are stored directly in the internal EEPROM of the ECG.

•

Are the data in the ECG lost if there is a power failure?

No, the data are permanently stored in the ECG. They are retained

even if the power failure is prolonged.

•

What happens if an ECG fails?

The ECG simply has to be replaced and adjusted to the appropri-

ate settings (the procedure depends on the control unit).

•

What happens if a control unit is faulty?

If the DALI interface voltage is lost, all ECGs take on the so-called

"system failure level" (ECG factory setting: 100 % light).

•

Can DALI be integrated in superordinate building manage-
ment systems (e.g. EIB or LON)?

Yes, by using gateways or control units with the appropriate inter-

face.

•

Is DALI a competitor to EIB or LON?

No, DALI is only a subsystem of the building management system

for controling the lighting.

•

Can 1…10 V components also be incorporated in a DALI
lighting control system?

Yes, by using DALI to 1…10 V converters.

•

Can existing 1…10 V lighting systems be upgraded with a
DALI controller?

Yes, a DALI to 1…10 V converter is needed for each 1…10 V lumi-

naire group (e.g. DALI CON 1…10 SO).

•

Can the wiring of the DALI ECG be checked on a building
site?

This depends on the control unit used. DALI ECGs that are still in

their factory setting always produce 100 % light when the mains
voltage (with protection) is applied.