Xylem IM117 R01 5 and Larger Submersible Pump User Manual

Page 13

Advertising
background image

13

6-10" THREE PHASE MOTORS

Motor

HP kW Volts Phase

Motor Dia.

S.F.

Rated Input

Service Factor

L.R.

Order No.

vs Flange Dia. Amps Watts Amps Watts Amps

6M058 5 3.7 200

17.5 4910 19.5 5610 124

6M052

5 3.7 230

15.0 4857 17.0 5520 110

6M054

5

3.7

460

7.5 4857 8.5 5520 55

6M078 7.5

5.5 200

25.4 7180 28.5 8230 158

6M072

7.5

5.5 230

22.0 7127 26.0 8140 144

6M074

7.5

5.5 460

11.0 7127 13.0 8140 72

6M108 10 7.5 200

33.3 9360 37.2 10700 236

6M102

10

7.5

230

29.0

9407

33.0

10730

208

6M104

10

7.5

460

14.5

9407

16.5

10730

104

6M158 15 11 200

47.4 13700 53.5 15710 347

6M152

15

11

230

3

6" x 6"

1.15

42.0

13700

46.0

15800

320

6M154

15 11 460

21.0 13700 23.0 15800 160

6M208 20 15 200

61.2 18040 69.5 20820 431

6M202

20 15 230

54.0 17930 60.0 20650 392

6M204

20 15 460

27.0 17930 30.0 20650 196

6M258 25

18.5 200

77.3 22740 87.5 26190 578

6M252

25

18.5 230

68.0 22470 76.0 25800 530

6M254

25

18.5 460

34.0 22470 37.0 25800 265

6M308 30 22 200

91.8 27000 104.0 31120 674

6M302

30 22 230

82.0 27130 94.0 31160 610

6M304

30 22 460

41.0 27130 47.0 31160 305

6M404

40

30

460

6" x 6"

53.0 35530 60.0 41100 340

66M504

50 37 460

70.0 45210 79.0 52380 465

86M504

50

37

460

8" x 6"

65.0 44360 73.0 51000 435

86M604

60 45 460

80.0 52850 90.0 60900 510

8M754

75

55

460

3

1.15

96.0

65900

109.0

76100

650

8M1004

100

75

460

8" x 8"

127.0 87600 145.0 101300 795

8M1254

125 90 460

160.0 110800 180.0 126000 980

8M1504

150 110 460

195.0 130700 220.0 152000 1060

10M2004

200

150

460

10 "x 10"

235.0

171100

270.0

198600

1260

5-30 HP, 3 Phase 230 and 460 Motors have adjustable voltage feature, change voltage plugs to convert from 230V to 460V

operation. Spare Change Plug Order No's are: PLUG-230V or PLUG-460V.

6" SINGLE PHASE MOTORS AND REQUIRED CONTROL BOXES

Motor

HP kW Volts Phase

Motor Dia.

S.F.

Rated Input Service Factor L.R.

Control Box

Order No.

vs Flange Dia. Amps Watts Amps Watts Amps Order No.

6M051

5

3.7

24

4987

27.5

5735

124

CB05MC (3R)

6M071

7.5

5.5

230

1

6” x 6”

1.15

36 7675 41 8950 167 CB07MC

(3R)

6M101

10

7.5

50

10135

58

11830

202

CB10MC (3R)

6M151

15

11

72

15180

85

18050

275

CB15MC (3R)

NEMA 3R control boxes will be replacing the current models.

Advertising