Xylem IM117 R01 5 and Larger Submersible Pump User Manual

Page 5

Advertising
background image

5

2.2 Assemble Pump End to Motor

Under no circumstance should the pump be run dry. Doing

so may damage internal parts. We suggest you check the

rotation on a three phase motor before assembling it to the

water end (pump). All 4" and 6" single phase motors should

rotate counterclockwise when viewed from the shaft end.

Rotation on three phase motors should match pump speci-

fications. Due to the high-starting torque the motor should

be secured in such a way as not to damage the motor but to

hold the motor from spinning.

Remove the cable guard from the pump (water end). Install

the motor shaft sand slinger if included with the water end in

the motor mounting hardware package. Attach the water end

to the motor. Align the wires in the cable guard and reinstall

it to the water end.

2.3 Install Check Valve(s)

Discharge heads are threaded with NPT pipe threads. All

models, without built-in check valves, require a spring

loaded check valve within 25' (7.5m) of the pump discharge

and below the drawdown level of the water supply. Motor

manufacturers recommend additional check valves every 200'

to 250' (70m) in the vertical discharge line. Check valves are

used to hold pressure in the system and to prevent backspin,

water hammer and upthrust.

Backspin is allowing water to flow back through the pump to

drain the system. It causes the impellers and motor rotor to

rotate in a reverse direction. This can cause premature thrust

bearing wear and if the motor starts during backspin the

shaft can be twisted or broken.

Water Hammer occurs when the lowest check valve is more

than 30' above the standing water level or the lower check

valve leaks and the check valve above holds. This creates a

partial vacuum (void) in the discharge piping. On the next

start, water moving at a very high velocity fills the void and

strikes the closed check valve and the stationary water in the

pipe above it, causing a hydraulic shock. This shock (water

hammer) can split pipes, break joints, and damage the pump

and motor. Water hammer is an easily detected noise. When

discovered the pump should be immediately shut down and

the installer contacted to resolve the problem.

Upthrust is an upward movement of the impellers and motor

shaft. It is caused by starting the pump at zero head due to

no check valve or a leaking check valve; or very low system

head due to a high static water level. Repeated upthrust can

cause premature failure of either or both the pump and the

motor. See 4.2

2.4 Installing Pump in Well

If you are using a torque arrestor, install it per the manufac-

turer’s installation instructions. On top feeding wells or large

diameter wells where water velocity will not cool the mo-

tor properly install a flow sleeve over the pump. See Table 3

– Required Cooling Flow.

Connect the discharge pipe to the pump discharge head.

Submersible pumps are capable of very high discharge pres-

sures, consult with your pipe supplier to determine the best

pipe material and schedule for each installation.

Lower the pump into the well. Set the pump at least 10' off

the bottom but above the screens. Protect the wires from

chafing on the well casing. Install a pitless adapter or similar

device at the wellhead. Consult the fitting manufacturer or

pitless supplier for specific installation instructions.

Using waterproof electrical tape, or wire ties, fasten the

wires to the drop pipe at 10' intervals. Make sure that the

tape does not loosen as it will block the pump suction if it

falls down the well.

2.5 Pressure Relief Valve

Pressure relief valves are mandatory (required) on any system

that is capable of producing over 100 psi or 230' TDH. In

an area where a water leak or blow-off may damage property

connect a drain line to the pressure relief valve. Run it to a

suitable drain or an area where the water will not damage

property.

2.6 Pressure Tank and Pressure Switch

(when used)

The pressure switch should be located at the tank cross tee

on a single tank and as close to the center as possible on

multiple tank installations. Multiple tank installations should

have a manifold pipe 1½ to 2 times the size of the supply

pipe from the pump. This is to reduce the friction head loss

or pressure differential in the manifold. Excessive losses

could cause switch chatter. There should be no filters, or

high loss fittings between the switch and the tank(s). Wide

open gate valves are allowed between the tank and switch.

2.7 Adjusting Tank Pre-Charge (when used)

Insure that the tank is empty of water. Use a high quality

pressure gauge to check the tank pre-charge pressure. The

pressure should be 2 psi below the pump cut-in (turn on)

pressure. As an example, a 30-50 psi system would use a

tank pre-charge of 28 psi.

Select an area where the temperature is above 34° F in which

to install the tank, pressure switch, and pressure relief valve.

The tank should be located in an area where a leak will not

damage property.

3.0 ELECTRICAL INSTRUCTIONS

3.1 General

Note: Do not power the unit or run the pump until all

electrical and plumbing connections are completed and the

pump is filled with water.

Always follow the National Electric Code (N.E.C.) in the

U.S., or the Canadian Electrical Code in Canada, as well as

all state, provincial, or local codes.

All electrical work must be performed by qualified

personnel. Some local laws require installation by only

“licensed installers”.

We suggest using only copper wire. Size wire from the charts

found in our ITT MAID, Motor Application & Installation

Manual, or an N.E.C.( National Electric Code) manual. If

discrepancies exist the N.E.C. in the U.S., and in Canada the

Canadian Electrical Code prevails.

3.0 ELECTRICAL INSTRUCTIONS

Advertising