Xylem IM117 R01 5 and Larger Submersible Pump User Manual

Page 15

Advertising
background image

15

THREE PHASE POWER UNBALANCE

THREE PHASE POWER UNBALANCE

A full three phase supply consisting of three individual

transformers or one three phase transformer is recom-

mended. “Open” delta or wye connections using only two

transformers can be used, but are more likely to cause poor

performance, overload tripping or early motor failure due to

current unbalance.
Check the current in each of the three motor leads and

calculate the current unbalance as explained below.
If the current unbalance is 2% or less, leave the leads as

connected.
If the current unbalance is more than 2%, current readings

should be checked on each leg using each of the three pos-

sible hook-ups. Roll the motor leads across the starter in the

same direction to prevent motor reversal.

To calculate percent of current unbalance:

A. Add the three line amp values together.

B. Divide the sum by three, yielding average current.

C. Pick the amp value which is furthest from the average

current (either high or low).

D. Determine the difference between this amp value

(furthest from average) and the average.

E. Divide the difference by the average.

Multiply the result by 100 to determine percent of

unbalance.

Current unbalance should not exceed 5% at service factor

load or 10% at rated input load. If the unbalance cannot be

corrected by rolling leads, the source of the unbalance must

be located and corrected. If, on the three possible hookups,

the leg farthest from the average stays on the same power

lead, most of the unbalance is coming from the power

source.
Contact your local power company to resolve the imbalance.

Hookup

1

Hookup

2

Hookup

3

Starter

Terminals L1 L2 L3 L1 L2 L3 L1 L2 L3


Motor

Leads

R B Y Y R B B Y R

T3 T1 T2 T2 T3 T1 T1 T2 T3

Example:

T3-R = 51 amps

T2-Y = 50 amps

T1-B = 50 amps

T1-B = 46 amps

T3-R = 48 amps

T2-Y = 49 amps

T2-Y = 53 amps

T1-B = 52 amps

T3-R = 51 amps

Total = 150 amps

Total = 150 amps

Total = 150 amps

÷ 3 = 50 amps

÷ 3 = 50 amps

÷ 3 = 50 amps

— 46 = 4 amps

— 48 = 2 amps

— 49 = 1 amps

4 ÷ 50 = .08 or 8%

2 ÷ 50 = .04 or 4%

1 ÷ 50 = .02 or 2%

Advertising