Section 3 Installation

Common Backpanel Mounted Units

Branch Circuit Protection

WARNING

!

b

rancH

c

ircuit

p

rotEction

r

EquirEd

!

p

rovidE

brancH

circuit

p

rotEction

in

accordancE

witH

tHE

n

ational

E

lEctrical

c

odE

. f

ailurE

to

providE

brancH

circuit

p

rotEction

in

accordancE

witH

tHE

nEc

may

rEsult

in

EquipmEnt

or

propErty

damagE

.

Drive Fuses

If specified as an option, drive input fuses will be

factory installed in the enclosure. If not factory sup-

plied, they must be provided by the installer as part

of installation.

Tools and Equipment Required

In addition to the standard tool kit, the tools and de-

vices in Table 3-1 are recommended for installation

of the unit.

TOOLS

Spreader bar capable of lifting up to 1000 lbs.

Max diameter 0.875 in.

Forklift, crane, hoist or other lifting device

capable of handling up to 1000 lbs. (Qualified

device operator available for operating the

equipment.)

Metric socket set: 7 - 19mm

Socket extensions: 4 & 6 in

Torx driver set: T10 - T40

Torque wrench: 6 - 170 in-lbs

Table 3-1. Tools and Equipment Required

Table 3-2. Connection Tightening Torques

Power (hp)

Torque (in-lbs)

Frame 200-240 V 380-480 V 525-600 V Line

Motor DC Brake Ground Relay

A2

2 - 5

3 - 5

3 - 5

17

17

17

28

5

A3

5

10

5 - 10

17

17

17

28

5

A5

1.5 - 5

1.5 - 10

1.5 - 10

17

17

17

28

5

B1 7.5 - 15

15 - 25

--

17

17

13

28

5

B2

20

30 - 40

--

22, 40 22, 40

32

29

5

C1

25 - 40

50 - 75

--

88

88

88

28

5

C2

50 - 60 100 - 125

--

124, 212 124, 212

124

29

5

D1

--

150-200

150-200

168

168

84

29

7

D2

--

250-350

250-400

168

168

84

29

7

Internal Option Panel Fuses

Use the specified fuse or an equivalent replacement

only for internal option panel fuses. Fuse options

include the drive disconnect and contactor fuses.

Figure 3-1. Drive Input Fuses