Warning, Branch circuit protection, Drive fuses – Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual
Page 12: Tools and equipment required, Internal option panel fuses

12
Section 3 Installation
Common Backpanel Mounted Units
Branch Circuit Protection
WARNING
!
b
rancH
c
ircuit
p
rotEction
r
EquirEd
!
p
rovidE
brancH
circuit
p
rotEction
in
accordancE
witH
tHE
n
ational
E
lEctrical
c
odE
. f
ailurE
to
providE
brancH
circuit
p
rotEction
in
accordancE
witH
tHE
nEc
may
rEsult
in
EquipmEnt
or
propErty
damagE
.
Drive Fuses
If specified as an option, drive input fuses will be
factory installed in the enclosure. If not factory sup-
plied, they must be provided by the installer as part
of installation.
Tools and Equipment Required
In addition to the standard tool kit, the tools and de-
vices in Table 3-1 are recommended for installation
of the unit.
TOOLS
Spreader bar capable of lifting up to 1000 lbs.
Max diameter 0.875 in.
Forklift, crane, hoist or other lifting device
capable of handling up to 1000 lbs. (Qualified
device operator available for operating the
equipment.)
Metric socket set: 7 - 19mm
Socket extensions: 4 & 6 in
Torx driver set: T10 - T40
Torque wrench: 6 - 170 in-lbs
Table 3-1. Tools and Equipment Required
Table 3-2. Connection Tightening Torques
Power (hp)
Torque (in-lbs)
Frame 200-240 V 380-480 V 525-600 V Line
Motor DC Brake Ground Relay
A2
2 - 5
3 - 5
3 - 5
17
17
17
28
5
A3
5
10
5 - 10
17
17
17
28
5
A5
1.5 - 5
1.5 - 10
1.5 - 10
17
17
17
28
5
B1 7.5 - 15
15 - 25
--
17
17
13
28
5
B2
20
30 - 40
--
22, 40 22, 40
32
29
5
C1
25 - 40
50 - 75
--
88
88
88
28
5
C2
50 - 60 100 - 125
--
124, 212 124, 212
124
29
5
D1
--
150-200
150-200
168
168
84
29
7
D2
--
250-350
250-400
168
168
84
29
7
Internal Option Panel Fuses
Use the specified fuse or an equivalent replacement
only for internal option panel fuses. Fuse options
include the drive disconnect and contactor fuses.
Figure 3-1. Drive Input Fuses