Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual

Page 45

Advertising
background image

45

39-63

High Suction Cut-Out

Pressure

0.0

Depends on

P3965

0.0

If a Suction Pressure source is selected

in P39-65 then this parameter sets the

pressure above which the timer in P39-

62 is started. If the timer expires while

the suction pressure remains above

this value then the pumps are not

needed and are shut off.

39-64

High Suction Reset

Pressure

0.0

Depends on

P3965

0.0

If the pumps have been shut off due

to High Suction Pressure and if the

pressure drops below this point then

the first pump will be turned on.

39-65

Suction Pressure Source

- No function

- Analog input 54

- Analog input X30/11

- Analog input X30/12

This parameter tells the controller

which analog input is connected to the

suction pressure sensor. Input scaling

for the sensor is defined in parameter

group P06-xx.

39-69

Suction Pressure

A display of the current Suction

Pressure.

39-7* PB Sys

Press

Feat.

39-70

High System Pressure

Level (Old Par. 774)

0.0 PSI

999999.0PSI

0.0 PSI If the pressure feedback signal

exceeds this value for the amount

of time set in parameter P39-71, the

controller will cause a system shutdown

and display ALARM, HIGH SYSTEM

PRESSURE. It will be necessary to

cycle power to the controller to reset

this alarm if P39-77 is set to Alarm Trip

Lock.

39-71

High System Pressure

Proof Time (Old Par. 775)

0s

999s

0s

This determines the amount of time

that the system must have pressure

greater than the value set in parameter

P39-70 before it goes into an alarm

condition.

39-72

Low System Pressure Level 0.0

Depends on

P3965

0.0

If a System Pressure source is selected

in P39-75 then this parameter sets the

pressure below which the timer in P39-

73 is started. If the timer expires while

the system Pressure remains below

this value then the action defined in

P39-76 is performed.

39-73

Low System Pressure Proof

Time

0s

60s

0s

This determines the amount of time

that the system pressure must be lower

than the value set in parameter P39-73

before it performs the action selected

by P39-76.

Table 6-2. Parameter 39-** Group, Detailed Description (continued)