WARNING 222, M2 Open Failed

The contactor that connects the drive to the motor

failed to open. The motor cannot be operated.

WARNING 223, M2 Close Failed

The contactor that connects the drive to the motor

failed to close. The motor cannot be operated.

WARNING 224, M3 Open Failed

The contactor that connects the motor to the

power line has failed to open.

WARNING 226, M3 Close Failed

The contactor that connects the motor to the

power line has failed to close. The motor cannot

be operated.

WARNING 227, Bypass Com Error

Communication between the main control card

and the bypass option has been lost. Motor con-

trol lost. It will be possible to run the motor using

Manual Bypass Override.

WARNING 228, APU Low Voltage

The option panel power supply has failed, or

there is a power problem.

WARNING 229, Motor Disconn

Terminal 3 on connector X57 of the ECB control

card shows an open. This generally means that

neither motor has been selected in contactor

motor select. Select a motor.

ALARM 252, LOW_SUCTION_CUT_OUT

Indicates that the pump suction pressure is

below the value specified in P39-61 for the time

specified in P39-60.

ALARM 253, LOW_SUCTION_CUT_OUT

Indicates that the System Pressure (output pres-

sure) is above the value specified by P39-70 for

the time specified in P39-71.

ALARM 254, HIGH_SYSTEM_PRESSURE

Indicates that the System Pressure (output pres-

sure) is below the value specified by P 39-72 for

the time specified in P39-73.

ALARM 255, ALL_ZONE_FAILURE

Indicates that all of the feedback sensors are

disconnected or have failed. The Drive proceeds

to Jog speed after the time specified in P39-45.

ALARM 256, ANALOG_INPUT_53_HIGH

Indicates that the designated Feedback is equal

to 20ma and may be shorted. It will no longer be

used after the time specified in P39-43

ALARM 257, ANALOG_INPUT_54_HIGH

Indicates that the designated Feedback is equal

to 20ma and may be shorted. It will no longer be

used after the time specified in P39-43

ALARM 258, ANALOG_INPUT_X30_11_HIGH

Indicates that the designated Feedback is equal

to 20ma and may be shorted. It will no longer be

used after the time specified in P39-43

Table 8-1. Warnings and Alarms (continued)

ALARM 259, ANALOG_INPUT_X30_12_HIGH

Indicates that the designated Feedback is equal

to 20ma and may be shorted. It will no longer be

used after the time specified in P39-43

ALARM 260, ANALOG_INPUT_53_LOW

Indicates that the designated Feedback is less

than 3ma and may be disconnected. It will no

longer be used after the time P39-42.

ALARM 261, ANALOG_INPUT_54_LOW

Indicates that the designated Feedback is less

than 3ma and may be disconnected. It will no

longer be used after the time P39-42.

ALARM 262, ANALOG_INPUT_X30_11_LOW

Indicates that the designated Feedback is less

than 3ma and may be disconnected. It will no

longer be used after the time P39-42.

ALARM 263, ANALOG_INPUT_X30_12_LOW

Indicates that the designated Feedback is less

than 3ma and may be disconnected. It will no

longer be used after the time P39-42.

ALARM 264, VFD_1_FAILED_TO_START

Indicates that the specified Drive has failed or is

not responding.

ALARM 265, VFD_2_FAILED_TO_START

Indicates that the specified Drive has failed or is

not responding.

ALARM 266, VFD_3_FAILED_TO_START

Indicates that the specified Drive has failed or is

not responding.

ALARM 267, VFD_4_FAILED_TO_START

Indicates that the specified Drive has failed or is

not responding.

ALARM 268, PUMP_1_FAILED_TO_START

Indicates that the pump suction pressure is

above the value specified in P39-63 for the time

specified in P39-62.

ALARM 269, PUMP_2_FAILED_TO_START

Indicates that the specified Pump is indicating

no difference in pressure between the pump

input and output.

ALARM 270, PUMP_3_FAILED_TO_START

Indicates that the specified Pump is indicating

no difference in pressure between the pump

input and output.

ALARM 271, PUMP_4_FAILED_TO_START

Indicates that the specified Pump is indicating

no difference in pressure between the pump

input and output.

ALARM 272, HIGH_SUCTION_CUT_OUT

Indicates that the pump suction pressure is

above the value specified in P39-63 for the time

specified in P39-62.