Modbus rtu point map (by function) – Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual

Page 66

Advertising
background image

66

Modbus RTU Point Map (by function)

Param

Number

Index

(Modbus

register

0x0009)

Status

Word Bit #

Modbus

Function

Code

Modbus

DESCRIPTION

RANGE/VALUE

SIZE IN

BITS

05

12

Pump Sequence Alternation

1 = Yes 0 = No

05

8

System Reset Request

1 = Yes 0 = No

05

7

System Start / Stop

1 = Start 0 = Stop

39-02

# 00

03

39020

System Start/Stop

1 = Start 0 = Stop

16

39-02

# 01

03

39020

Pump Standby Enabled

1 = Enabled 0 = Disabled

16

39-02

# 02

03

39020

General Alarm Output

1 = Failure 0 = O.K.

16

39-02

# 04

03

39020

Pump #1 On/Off

1 = On 0 = Off

16

39-02

# 05

03

39020

Pump #2 On/Off

1 = On 0 = Off

16

39-02

# 06

03

39020

Pump #3 On/Off

1 = On 0 = Off

16

39-02

# 07

03

39020

Pump #4 On/Off

1 = On 0 = Off

16

39-02

# 08

03

39020

Pump #1 Configured

1 = Configured 0 = Disabled

16

39-02

# 09

03

39020

Pump #2 Configured

1 = Configured 0 = Disabled

16

39-02

# 10

03

39020

Pump #3 Configured

1 = Configured 0 = Disabled

16

39-02

# 11

03

39020

Pump #4 Configured

1 = Configured 0 = Disabled

16

39-02

# 12

03

39020

Pump #1 Running In Bypass Mode 1 = In Bypass 0 = VFD

16

39-02

# 13

03

39020

Pump #2 Running In Bypass Mode 1 = In Bypass 0 = VFD

16

39-02

# 14

03

39020

Pump #3 Running In Bypass Mode 1 = In Bypass 0 = VFD

16

39-02

# 15

03

39020

Pump #4 Running In Bypass Mode 1 = In Bypass 0 = VFD

16

16-03

#03

03

16030

System Reset Required

1 = Yes 0 = No

32

16-93

#20

03

16930

All Zone Failure

1 = Failure 0 = O.K.

32

16-93

#21

03

16930

Analog Input #1 High Failure

1 = Failure 0 = O.K.

32

16-93

#22

03

16930

Analog Input #2 High Failure

1 = Failure 0 = O.K.

32

16-93

#23

03

16930

Analog Input #3 High Failure

1 = Failure 0 = O.K.

32

16-93

#24

03

16930

Analog Input #4 High Failure

1 = Failure 0 = O.K.

32

16-93

#25

03

16930

Analog Input #1 Low Failure

1 = Failure 0 = O.K.

32

16-93

#26

03

16930

Analog Input #2 Low Failure

1 = Failure 0 = O.K.

32

16-93

#27

03

16930

Analog Input #3 Low Failure

1 = Failure 0 = O.K.

32

16-93

#28

03

16930

Analog Input #4 Low Failure

1 = Failure 0 = O.K.

32

16-91

#20

03

16910,1 Low System Alarm

1 = Failure 0 = O.K.

32

16-91

#21

03

16910,1 High System Alarm

1 = Failure 0 = O.K.

32

16-91

#22

03

16910,1 Low Suction Alarm

1 = Failure 0 = O.K.

32

16-54

03

16540,1 Process Variable #1

0 to Span (in Technologic User Setup Menu)

32

16-55

03

16550,1 Process Variable #2

0 to Span (in Technologic User Setup Menu)

32

16-56

03

16560,1 Process Variable #3

0 to Span (in Technologic User Setup Menu)

32

16-57

03

16570,1 Process Variable #4

0 to Span (in Technologic User Setup Menu)

32