Required Drive Programming

Both Master and Follower drives require basic opera-

tional programming, which includes nameplate motor

data for the motor being operated and basic motor

operation speeds. Enter this data in accordance with

the following procedures. See the Section 5, User

Interface in this manual for detailed programming in-

structions. This data needs to be entered with power

ON but prior to operating the system.

notE

p

rEss

q

uick

m

Enu

or

m

Enu

kEy

on

drivE

kEypad

to

accEss

programming

paramEtErs

. u

sE

up

/

down

arrow

kEys

on

kEypad

to

scroll

tHrougH

paramEtEr

lists

. p

rEss

ok

kEy

to

EntEr

paramEtEr

and

prEss

ok

kEy

again

to

accEss

paramEtEr

data

. o

ncE

paramEtEr

is

EntErEd

,

usE

sidE

arrow

kEys

to

scroll

sidEways

and

up

/

down

arrow

kEys

to

incrEasE

or

dEcrEasE

a

valuE

. p

rEss

ok

kEy

to

storE

sEtting

or

c

ancEl

kEy

to

cancEl

. u

sE

b

ack

kEy

to

rEturn

to

mEnu

. p

rEss

i

nfo

kEy

to

accEss

sHort

dEscription

of

currEnt

paramEtEr

option

. s

EE

u

sEr

i

ntErfacE

sEction

in

tHis

manual

for

dEtailEd

instructions

.

1. Access Quick Menu on Master drive keypad.

2. Go to parameter group Q2 Motor Setup and

press OK key.

3. Scroll down list of all nine important motor

data parameters in this section and enter

motor data from motor nameplate, along

with ramp up and down times, and high and

low motor speed limits. It is important for

maximum system efficiency that this data

be accurate. It is recommended to set ramp

times to 10 seconds in parameters 3-41 and

3-42.

4. Repeat steps 2 and 3 for each Follower

drive in system.

For Master drives only:

1. Press Quick Menu key and go to parameter

group Q3, System Setup. Press OK key to

enter.

2. Scroll down parameter list and either

confirm default setting is appropriate to

system application, or enter new setting, as

required.

3. In Quick Menu, go to Q1, My Personal Menu

and press OK key to enter.

4. Scroll down parameter list and enter setpoint

values. Ensure parameter 39-55, Local/

Remote, is set for local operation.

5. In Main Menu, go to parameter 39-** Tech

502 Setup, and press OK key to enter. In

parameter 39-0*, Configuration, scroll to

39-00, Auto Assign I/O Pins and scroll to

the system type for the master drive being

programmed. Press OK key to select. See

Table 6-2, Parameter 39-** Group, Detailed

Description for more details.