Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual
Page 39

39
No.
Name
Min
Max
Default
Description
39-0*
Config.
39-00
Auto Assign I/O Pins
0 - Done
1 - A0
2 - C0 - 1 Followers
3 - D0 - 1 Follower
4 - D0 - 2 Followers
5 - D0 - 3 Followers
6 - A1
7 - B3
8 - C4
9 - D4
10 - 70X - 1CS
11 - 70X - 2CS
12 - 70X - 3CS
13 - Follower
0
13
0
Selecting one of these Configurations
will automatically set the input and
output parameters and default values
correctly for the configuration.
39-02
System Status Word
Status flags used for fieldbus
communications
39-03
System Operating Mode
0
2
1
Status used for fieldbus
communications
0 - Manual
1 - Auto
2 - Auto Bypass
39-04
Warning Status 1
Warning flags used for fieldbus
communications
39-05
Warning Status 2
Warning flags used for fieldbus
communications
39-06
Last Configuration Setting
0
13
13
Last Configuration setting selected
through P39-00. Warning: Individual
parameter settings of the configuration
may be changed manually so there is
no guarantee that it is still set to this
standard configuration.
39-1* Stage/
Destage
39-10
Stage Speed (Old Par. 750)
0%
100%
95%
When a variable speed pump reaches
this percentage of maximum speed,
the controller will start a timer, set in
parameter P39-11. After this timer
expires, the controller will stage on
another pump.
39-11
Stage Proof Timer (Old Par.
751)
0s
999s
30s
After a variable speed pump reaches
the speed percentage set in parameter
P39-10, this timer will start. After this
timer expires the controller will stage on
an additional pump.
Table 6-2. Parameter 39-** Group, Detailed Description