Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual

Page 39

Advertising
background image

39

No.

Name

Min

Max

Default

Description

39-0*

Config.

39-00

Auto Assign I/O Pins

0 - Done

1 - A0

2 - C0 - 1 Followers

3 - D0 - 1 Follower

4 - D0 - 2 Followers

5 - D0 - 3 Followers

6 - A1

7 - B3

8 - C4

9 - D4

10 - 70X - 1CS

11 - 70X - 2CS

12 - 70X - 3CS

13 - Follower

0

13

0

Selecting one of these Configurations

will automatically set the input and

output parameters and default values

correctly for the configuration.

39-02

System Status Word

Status flags used for fieldbus

communications

39-03

System Operating Mode

0

2

1

Status used for fieldbus

communications

0 - Manual

1 - Auto

2 - Auto Bypass

39-04

Warning Status 1

Warning flags used for fieldbus

communications

39-05

Warning Status 2

Warning flags used for fieldbus

communications

39-06

Last Configuration Setting

0

13

13

Last Configuration setting selected

through P39-00. Warning: Individual

parameter settings of the configuration

may be changed manually so there is

no guarantee that it is still set to this

standard configuration.

39-1* Stage/

Destage

39-10

Stage Speed (Old Par. 750)

0%

100%

95%

When a variable speed pump reaches

this percentage of maximum speed,

the controller will start a timer, set in

parameter P39-11. After this timer

expires, the controller will stage on

another pump.

39-11

Stage Proof Timer (Old Par.

751)

0s

999s

30s

After a variable speed pump reaches

the speed percentage set in parameter

P39-10, this timer will start. After this

timer expires the controller will stage on

an additional pump.

Table 6-2. Parameter 39-** Group, Detailed Description