Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual
Page 71

71
Point
Num.
Descriptor
Factory Default
(SI)
Units
(SI)
Slope
(SI)
On
Text
Off
Text
R
ange
Max
V
alue
(SI)
Min
V
alue
(SI)
Point
Type
Class
Type
R
ead
Only
Par
ameter#
Bit
66
PID D TIME
0
SEC
0.01
0
16383
1000
0
1
LAO
No
2095
67
--Free P
oint
--
68
FB FUNCTION
7
1
0
255
255
0
1
LDO
No
2020
69
SETPOINT 1
0
UNIT
0.1
-1638.3
32767
1638300
1
LAO
No
2021
70
SETPOINT 2
0
UNIT
0.1
-1638.3
32767
1638300
1
LAO
No
2022
71
SETPOINT 3
0
UNIT
0.1
-1638.3
32767
1638300
1
LAO
No
2023
72
SETPOINT 4
0
UNIT
0.1
-1638.3
32767
1638300
1
LAO
No
2024
73
--Free P
oint
--
75
BUS FBK 1
0
PCT
0.01
-163.83
32767
16383
-16383
1
LAO
No
894
76
BUS FBK 2
0
PCT
0.01
-163.83
32767
16383
-16383
1
LAO
No
895
77
BUS FBK 3
0
PCT
0.01
-163.83
32767
16383
-16383
1
LAO
No
896
78
--Free P
oint
--
80
DRV ENA PUMP1
0
1
0
ENABLE
DIS
ABL
255
255
0
3
LDI
Yes
1603
2
81
DRV RD
Y
PUMP1
0
1
0
READ
Y
NO
TRD
Y
255
255
0
3
LDI
Yes
1603
1
82
DRV CTL PUMP1
0
1
0
READ
Y
NO
TRD
Y
255
255
0
3
LDI
Yes
1603
0
83
--Free P
oint
--
88
LOW SUCTION
0
1
0
ALARM
OK
32767
32767
0
3
LDI
Yes
3905
8
89
HI SYS PRES
S
0
1
0
ALARM
OK
32767
32767
0
3
LDI
Yes
3905
7
90
OK W
ARNING
0
1
0
W
ARN
OK
255
255
0
3
LDI
Yes
1603
7
91
CRNT W
ARNING
0
1
0
32767
32767
0
3
LAI
Yes
92
GEN ALARM
0
1
0
FA
UL
T
OK
255
255
0
1
LDO
Yes
3902
2
93
LA
ST F
A
UL
T
0
1
0
255
255
0
3
LAI
Yes
1530
94
RESET F
A
UL
T
0
1
0
YES
OK
255
255
0
1
LDO
No
1685
7
95
ACTIVE SETUP
0
1
0
255
255
0
3
LAI
Yes
10
96
--Free P
oint
--
99
ERROR ST
A
TUS
0
1
0
255
255
0
3
LAI
Yes