Metasys n2 point map – Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual
Page 63

63
Metasys N2 Point Map
NPT
NPA
POINT DESCRIPTION
RANG/VALUE
UNITS Size in
Bits
BI
162
System Start/Stop
1 = Start 0 = Stop
1
BI
163
Pump Standby Enabled
1 = Enabled 0 = Disabled
1
BI
164
General Alarm Output
1 = Failure 0 = O.K.
1
BI
166
Pump #1 On/Off
1 = On 0 = Off
1
BI
167
Pump #2 On/Off
1 = On 0 = Off
1
BI
168
Pump #3 On/Off
1 = On 0 = Off
1
BI
169
Pump #4 On/Off
1 = On 0 = Off
1
BI
170
Pump #1 Configured
1 = Configured 0 = Disabled
1
BI
171
Pump #2 Configured
1 = Configured 0 = Disabled
1
BI
172
Pump #3 Configured
1 = Configured 0 = Disabled
1
BI
173
Pump #4 Configured
1 = Configured 0 = Disabled
1
BI
174
Pump #1 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
1
BI
175
Pump #2 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
1
BI
176
Pump #3 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
1
BI
177
Pump #4 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
1
BI
155
Pump #1 Bypass Overload
1 = Failure 0 = O.K.
1
BI
10
System Reset Required
1 = Yes 0 = No
1
BI
146
All Zone Failure
1 = Failure 0 = O.K.
1
BI
145
Analog Input #1 High Failure
1 = Failure 0 = O.K.
1
BI
144
Analog Input #2 High Failure
1 = Failure 0 = O.K.
1
BI
143
Analog Input #3 High Failure
1 = Failure 0 = O.K.
1
BI
142
Analog Input #4 High Failure
1 = Failure 0 = O.K.
1
BI
141
Analog Input #1 Low Failure
1 = Failure 0 = O.K.
1
BI
140
Analog Input #2 Low Failure
1 = Failure 0 = O.K.
1
BI
139
Analog Input #3 Low Failure
1 = Failure 0 = O.K.
1
BI
138
Analog Input #4 Low Failure
1 = Failure 0 = O.K.
1
BI
178
Pump #1 VFD Failure
1 = Failure 0 = O.K.
1
BI
179
Pump #2 VFD Failure
1 = Failure 0 = O.K.
1
BI
180
Pump #3 VFD Failure
1 = Failure 0 = O.K.
1
BI
181
Pump #4 VFD Failure
1 = Failure 0 = O.K.
1