Metasys n2 point map – Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual

Page 63

Advertising
background image

63

Metasys N2 Point Map

NPT

NPA

POINT DESCRIPTION

RANG/VALUE

UNITS Size in

Bits

BI

162

System Start/Stop

1 = Start 0 = Stop

1

BI

163

Pump Standby Enabled

1 = Enabled 0 = Disabled

1

BI

164

General Alarm Output

1 = Failure 0 = O.K.

1

BI

166

Pump #1 On/Off

1 = On 0 = Off

1

BI

167

Pump #2 On/Off

1 = On 0 = Off

1

BI

168

Pump #3 On/Off

1 = On 0 = Off

1

BI

169

Pump #4 On/Off

1 = On 0 = Off

1

BI

170

Pump #1 Configured

1 = Configured 0 = Disabled

1

BI

171

Pump #2 Configured

1 = Configured 0 = Disabled

1

BI

172

Pump #3 Configured

1 = Configured 0 = Disabled

1

BI

173

Pump #4 Configured

1 = Configured 0 = Disabled

1

BI

174

Pump #1 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

1

BI

175

Pump #2 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

1

BI

176

Pump #3 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

1

BI

177

Pump #4 Running In Bypass Mode

1 = In Bypass 0 = Not In Bypass

1

BI

155

Pump #1 Bypass Overload

1 = Failure 0 = O.K.

1

BI

10

System Reset Required

1 = Yes 0 = No

1

BI

146

All Zone Failure

1 = Failure 0 = O.K.

1

BI

145

Analog Input #1 High Failure

1 = Failure 0 = O.K.

1

BI

144

Analog Input #2 High Failure

1 = Failure 0 = O.K.

1

BI

143

Analog Input #3 High Failure

1 = Failure 0 = O.K.

1

BI

142

Analog Input #4 High Failure

1 = Failure 0 = O.K.

1

BI

141

Analog Input #1 Low Failure

1 = Failure 0 = O.K.

1

BI

140

Analog Input #2 Low Failure

1 = Failure 0 = O.K.

1

BI

139

Analog Input #3 Low Failure

1 = Failure 0 = O.K.

1

BI

138

Analog Input #4 Low Failure

1 = Failure 0 = O.K.

1

BI

178

Pump #1 VFD Failure

1 = Failure 0 = O.K.

1

BI

179

Pump #2 VFD Failure

1 = Failure 0 = O.K.

1

BI

180

Pump #3 VFD Failure

1 = Failure 0 = O.K.

1

BI

181

Pump #4 VFD Failure

1 = Failure 0 = O.K.

1