Bell & Gossett 176R0649C Technologic 502 Series Pump Controller User Manual

Page 53

Advertising
background image

53

WARNING 1, 10 volts low

The control card voltage is below 10V from

terminal 50.

Remove some of the load from terminal 50, as

the 10V supply is overloaded. Max. 15 mA or

minimum 590 ohms.

This condition can be caused by a short in a

connected potentiometer or improper wiring of

the potentiometer.

Troubleshooting: Remove the wiring from

terminal 50. If the warning clears, the problem is

with the customer wiring. If the warning does not

clear, replace the control card.

WARNING/ALARM 2, Live zero error

This warning or alarm will only appear if pro-

grammed by the user in parameter 6-01 Live

Zero Timeout Function. The signal on one of the

analog inputs is less than 50% of the minimum

value programmed for that input. This condition

can be caused by broken wiring or faulty device

sending the signal.

Troubleshooting:

Check the connections on all the analog input

terminals. Control card terminals 53 and 54 for

signals, terminal 55 common. Make sure that

the controller programming and switch settings

match the analog signal type.

WARNING/ALARM 3, No motor

No motor has been connected to the output of

the controller. This warning or alarm will only

appear if programmed by the user in parameter

1-80 Function at Stop.

Troubleshooting: Check the connection be-

tween the controller and the motor.

WARNING/ALARM 4, Mains phase loss

A phase is missing on the supply side, or the

mains voltage imbalance is too high. This mes-

sage also appears for a fault in the input rectifier

on the controller. Options are programmed at

parameter 14-12 Function at Mains Imbalance.

Troubleshooting: Check the supply voltage and

supply currents to the controller.

WARNING 5, DC link voltage high

The intermediate circuit voltage (DC) is higher

than the high voltage warning limit. The limit is

dependent on the controller voltage rating. The

controller is still active.

WARNING 6, DC link voltage low

The intermediate circuit voltage (DC) is lower

than the low voltage warning limit. The limit is

dependent on the controller voltage rating. The

controller is still active.

WARNING/ALARM 7, DC overvoltage

If the intermediate circuit voltage exceeds the

limit, the controller trips after a time.

Troubleshooting:

Connect a brake resistor

Extend the ramp time

Change the ramp type

Activate functions in parameter 2-10 Brake

Function

Increase parameter 14-26 Trip Delay at Inverter

Fault

WARNING/ALARM 8, DC undervoltage

If the intermediate circuit voltage (DC) drops be-

low the undervoltage limit, the controller checks

if a 24V backup supply is connected. If no 24V

backup supply is connected, the controller trips

after a fixed time delay. The time delay varies

with unit size.

Troubleshooting:

Make sure that the supply voltage matches the

controller voltage.

WARNING/ALARM 9, Inverter overloaded

The controller is about to cut out because of an

overload (too high current for too long).

The counter for electronic, thermal inverter

protection gives a warning at 98% and trips at

100%, while giving an alarm. The controller can-

not be reset until the counter is below 90%. The

fault is that the controller is overloaded by more

than 100% for too long.

Troubleshooting:

Compare the output current shown on the LCP

with the controller rated current.

Compare the output current shown on the LCP

with measured motor current.

Display the Thermal Drive Load on the LCP

and monitor the value. When running above the

controller continuous current rating, the coun-

ter should increase. When running below the

controller continuous current rating, the counter

should decrease.

WARNING/ALARM 10, Motor overload temperature

According to the electronic thermal protection

(ETR), the motor is too hot. Select whether the

controller should give a warning or an alarm

when the counter reaches 100% in parameter

1-90 Motor Thermal Protection. The fault is that

the motor is overloaded by more than 100% for

too long.

Troubleshooting:

Check if motor is overheating.

If the motor is mechanically overloaded.

Table 8-1. Warnings and Alarms

Advertising