Manual, Level transmitter as signal amplifier – Xylem MJK 713 Open Channel Flowmeter User Manual

Page 14

Advertising
background image

14

Manual

US 3.10 713 Flow Converter 1210 - Sw 833062

MJK North America, Inc.
37 Sherwood Terrace, #126
Lake Bluff, Il 60044
Tel.: 847-482-8655
Fax: 847-482-8654
[email protected]
www.mjk.com

Electrical mounting

MJK 713 must not be connected to the power supply

before the ultrasonic sensor / pressure transmitter is

mounted and connected correctly.

MJK 713 is supplied from the mains on terminal
“0” and “P”.

Current regulations for conductor and fuse dimensions

should always be observed.

Remove the lid to gain access to the terminals.

Relay out 1

Relay out 2

Relay out 3

Relay out 4

Power
supply

Curr

ent output

(0 / 4 - 20 mA)

Totalizer output

Standard cable length 40 ft.

(Can be extended to max.150 ft. using

MJK no. 690010 cable.

No. 1 = brown

No. 2 = red

No. 3 = orange

No. 4 = yellow

No. 5 = black

MJK 713 2500 Flowmeter

Ultrasonic Sensor

MJK 713 System Package 1
MJK 713 2500 with ultrasonic sensor

MJK 713 System Package 3
MJK 713 3000 with hydrostatic level transmitter

Note: 1: Conduit hubs are to beconnected to the

conduit prior to the connection to the enclosure.

2: Terminal tightening torque = 0.5 Nm.

By looping the 4-20 mA signal through one of the relay
outputs on the Shuttle

®

Level Transmitter, a system

failure on the Shuttle

®

Level Transmitter will trig a

system failure message on the MJK 713. Note that
the Shuttle

®

must be programmed as described in

appendix E in order to achieve this function.

Ultrasonic Sensor

MJK 713 3000 Flowmeter

Shuttle

®

Level Transmitter

Power
supply

MJK 713 System Package 2
MJK 713 3000 with ultrasonic sensor using Shuttle

®

Level Transmitter as signal amplifier

Power
supply

No. 1 = red

No. 2 = brown

No. 3 = black

Pressure Transmitter