Programming modules – Franklin Fueling Systems TS 550 evo Fuel Management System Programming Guide User Manual

Page 21

Advertising
background image

21

Programming Modules

The Fuel Management System is composed of a custom set of modules. Each module has individual characteristics. 

Parameters must be set to match the site configuration. The programming table below will assist in this setup.
IO Modules

The Input / Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage inputs that can 

range from 3 to 240 volts. In addition to the AC / DC inputs, the IO module also includes four 4-20mA signal outputs.

Group Name

Parameter

Name

Parameter

Default

Description

Parameter Input

IO Modules

Module #

Inputs

Channels

(0)

The number of AC or DC inputs physically wired to the gauge.

0-8

Channel #

Name

(Input 1)

Descriptive name used to identify the input.

abc #

Enabled

(Yes)

Enables the input.

Yes / No

Active State

(High)

High will activate channel when high voltage is present. 

Low will activate channel with no voltage present.

High / Low

Action

(None)

Create an alarm or event timestamp  .

None

Alarm

Event

Outputs

Channels

(0)

Number of 4-20mA channels in use per module.

0-4

Channel #

Name

(output 1)

Descriptive name used to identify the output 

abc

Enable

(Yes)

Yes if the channel is in use

Yes / No

AC Input Modules

The AC Input Module is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can 

be used for dispenser hook isolation, vapor processor input, or as generic AC inputs.

Group Name

Parameter Default

Parameter

Default

Description

Parameter

Input

AC Input Modules

Module #

Channels

(0)

Number of channels in use per module.

0-12

Channel #

Name

(AC Input 1)

Given name of channel.

abc #

Enabled

(Yes)

Yes if channel is used.

Yes / No

Active State

(High)

High will activate channel when high voltage 

is present. Low will activate channel with no 

voltage present.

High / Low

Action Setup

None

Create an alarm or event timestamp

None, Alarm, 

Event

Probe Modules

The Probe Module gather data from probes or TS-DMS sensors. This information is processed by the Controller Module 

for use in inventory, reconciliation, V/L Ratio calculation, TS-DMS sensor alarms and to provide information for reports.

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

Probe Modules

Module #

Channels

(0)

Number of channels in use per module.

0-12

Channel #

Name

(Probe 1)

Given Name of Probe.

abc #

Type

(TS-LL2)

Type of device connected.

TS-VFM

TS-LL2

TS-DMS

Monthly Compliance

(Yes)

Select Yes if this sensor is to appear on the 

Compliance page and in the Regulatory report  

Yes / No