Programming Modules
The Fuel Management System is composed of a custom set of modules. Each module has individual characteristics.
Parameters must be set to match the site configuration. The programming table below will assist in this setup.
IO Modules
The Input / Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage inputs that can
range from 3 to 240 volts. In addition to the AC / DC inputs, the IO module also includes four 4-20mA signal outputs.
Group Name
Parameter
Name
Parameter
Default
Description
Parameter Input
IO Modules
Module #
Inputs
Channels
(0)
The number of AC or DC inputs physically wired to the gauge.
0-8
Channel #
Name
(Input 1)
Descriptive name used to identify the input.
abc #
Enabled
(Yes)
Enables the input.
Yes / No
Active State
(High)
High will activate channel when high voltage is present.
Low will activate channel with no voltage present.
High / Low
Action
(None)
Create an alarm or event timestamp .
None
Alarm
Event
Outputs
Channels
(0)
Number of 4-20mA channels in use per module.
0-4
Channel #
Name
(output 1)
Descriptive name used to identify the output
abc
Enable
(Yes)
Yes if the channel is in use
Yes / No
AC Input Modules
The AC Input Module is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can
be used for dispenser hook isolation, vapor processor input, or as generic AC inputs.
Group Name
Parameter Default
Parameter
Default
Description
Parameter
Input
AC Input Modules
Module #
Channels
(0)
Number of channels in use per module.
0-12
Channel #
Name
(AC Input 1)
Given name of channel.
abc #
Enabled
(Yes)
Yes if channel is used.
Yes / No
Active State
(High)
High will activate channel when high voltage
is present. Low will activate channel with no
voltage present.
High / Low
Action Setup
None
Create an alarm or event timestamp
None, Alarm,
Event
Probe Modules
The Probe Module gather data from probes or TS-DMS sensors. This information is processed by the Controller Module
for use in inventory, reconciliation, V/L Ratio calculation, TS-DMS sensor alarms and to provide information for reports.
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
Probe Modules
Module #
Channels
(0)
Number of channels in use per module.
0-12
Channel #
Name
(Probe 1)
Given Name of Probe.
abc #
Type
(TS-LL2)
Type of device connected.
TS-VFM
TS-LL2
TS-DMS
Monthly Compliance
(Yes)
Select Yes if this sensor is to appear on the
Compliance page and in the Regulatory report
Yes / No