25

Relay Modules

The Relay Modules come in two styles: a 10 amp module and a 2 amp module. The 2 amp module is a non-intrinscally 

module that has 8 identical 2 amp Form C output relays and the 10 amp module has 6 identical 10 amp Form C output 

relays. Each channel has a fuse and three terminals. Each channel can be configured as NO or NC with the power off by 

wiring to the appropriate terminals.

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

Relay Modules

Module #

10 Amp 

Channels

(No)

(0)

Select Yes if this is the 10 Amp relay module.

Number of relays used on this module.

Yes / No

0-8 (2 Amp 

module)

0-6 (10 Amp 

Module)

Channel #

Name

(Relay 1)

Given name of the channel.

abc#

Enabled

(Yes)

Yes if the channel is in use.

Yes / No

Type

(Unknown)

Equipment connected to the relays output.

Unknown 

Submersible

Alarm 

Solenoid

Dispenser

Other

Polarity

(Normal)

Allow the polarity to be inverted from normally closed to normally 

open, changing how the relay operates with a loss of system 

power.

Normal, Invert

Logic

(OR Logic)

The type of logic that the gate will use to process incoming signals.

OR, AND, XOR

Physically Wired As (Normally Open)

How the relay is wired externally.

NO, NC

Number of inputs

(0)

Number of devices that can control the relay.

1-32

Input #

Type

(Unknown)

Type of module that is sending the signal to control the relay.

Unknown

Controller

Power Supply

AC Input 

IO

Probe

2-wire Sensor

3-wire Sensor

4-20 mA

Advertising