Franklin Fueling Systems TS 550 evo Fuel Management System Programming Guide User Manual

Page 24

Advertising
background image

24

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

Relays

Channel #

Name

(Relay 1)

Given name of the relay.

abc#

Enabled

(Yes)

Whether the Relay is Enabled or not.

Yes  /No

Type

(Unknown)

Equipment connected to the relays output.

Unknown 

Submersible

Alarm 

Solenoid

Dispenser

Other

Polarity

(Normal)

Allow the polarity to be inverted from normally closed to 

normally open, changing how the relay operates with a loss 

of system power.

Normal, Invert

Logic

(OR Logic)

The type of logic that the gate will use to process incoming 

signals. In OR, if any combination of inputs is active, the 

relay is active. With AND, when all inputs are active, the 

relay is active. In XOR, if all inputs are in the same state 

(on / off), the relay is inactive.

OR, AND, XOR

Physically Wired As

(Normally 

Open)

How the relay is wired internally.

NO, NC

Number of inputs

(0)

Number of devices that can control the relay.

0-32

Input #

Type

(Unknown 

Module)

Type of module that is sending the signal to control the 

relay.

Unknown

Controller

Power Supply

IO

AE

4-20 

Probe

2-wire Sensor

3-wire Sensor

Channel #

Name

(LV Input 1)

Given name of input.

abc#

Enabled

(Yes)

Whether the input is Enabled or not.

Yes/No

Active State

(high)

High will activate channel when high voltage is present. Low 

will activate channel with no voltage present.

High / Low

Action

(None)

Create an alarm or event with a timestamp

None 

Alarm 

Event