Franklin Fueling Systems TS 550 evo Fuel Management System Programming Guide User Manual
Page 24

24
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
Relays
Channel #
Name
(Relay 1)
Given name of the relay.
abc#
Enabled
(Yes)
Whether the Relay is Enabled or not.
Yes /No
Type
(Unknown)
Equipment connected to the relays output.
Unknown
Submersible
Alarm
Solenoid
Dispenser
Other
Polarity
(Normal)
Allow the polarity to be inverted from normally closed to
normally open, changing how the relay operates with a loss
of system power.
Normal, Invert
Logic
(OR Logic)
The type of logic that the gate will use to process incoming
signals. In OR, if any combination of inputs is active, the
relay is active. With AND, when all inputs are active, the
relay is active. In XOR, if all inputs are in the same state
(on / off), the relay is inactive.
OR, AND, XOR
Physically Wired As
(Normally
Open)
How the relay is wired internally.
NO, NC
Number of inputs
(0)
Number of devices that can control the relay.
0-32
Input #
Type
(Unknown
Module)
Type of module that is sending the signal to control the
relay.
Unknown
Controller
Power Supply
IO
AE
4-20
Probe
2-wire Sensor
3-wire Sensor
Channel #
Name
(LV Input 1)
Given name of input.
abc#
Enabled
(Yes)
Whether the input is Enabled or not.
Yes/No
Active State
(high)
High will activate channel when high voltage is present. Low
will activate channel with no voltage present.
High / Low
Action
(None)
Create an alarm or event with a timestamp
None
Alarm
Event