2 enclosure grounding, 0 site preparation, continued – Alpha Technologies PN-4 User Manual

Page 12

Advertising
background image

031-103-B0-004, Rev. D

12

#6 AWG

#2 AWG

Two 8’ ground
rods placed a min.
of 6’ apart

Opening

for

Sweeps

Opening

for

Sweeps

Opening

for

Sweeps

2 Feet

Min.

Enclosure Footprint

Connection Made With

Burndy Connector

P/N YGHP58C2W-2TN

Connection Made With
Burndy Connector
P/N YGHR58C2W

3.0

Site Preparation, continued

3.2 Enclosure

Grounding

Lightning Protection (Optional)

1

1/2" x 8' copper ground rod, four places, driven about 2 feet (typical) from the corners of the pad.

2

#2 bare copper wire loop terminated to each ground rod and buried below grade 2 to 12 inches.
Corrosion-proof connections (25+ year life-span) and hardware suitable for direct burial MUST be
used.

3

#2 bare copper wire from loop to the enclosure.

4

When the electrical supply is a primary service (not a secondary or feeder service) a #2 bare copper
wire must be bond the lightning protection loop to the Grounding Electrode Conductor where they are
closest.

Service Grounding (required)

5

#6 bare copper wire from Service Neutral/Ground Bar with 2 ground rods located 6' apart.

1

4

5

2

3

Fig. 3-3, Suggested Grounding, PN-3 and PN-4