Alpha Technologies PN-4 User Manual

Page 27

Advertising
background image

27

031-103-B0-004, Rev. D

4.0 Installation,

continued

4.5

Battery Installation Procedure, continued

4.5.1 Connecting the Battery Remote Temperature Sensor (RTS)

The Remote Temperature Sensor (RTS) wiring connects to Temperature Sensor
Input connector of XM2 Power Supply. Tape the sensor to the side of the middle
battery in the string, so that the fl at side of the sensor is fl ush to the side of the
battery.

To prevent incorrect temperature readings, attach the Battery Temperature Sensor
associated with each XM2 Power Supply on different batteries.

Fig. 4-18, Battery Temperature Sensor Mounting Location

6.00"

Center of Battery