Alpha Technologies PN-4 User Manual

Page 16

Advertising
background image

031-103-B0-004, Rev. D

16

1

Bond made by bonding screw only if no other service panel is used (must be installed on site only if
primary service entrance).

4.0 Installation,

continued

4.1

Utility Powering, continued

4.1.1 Connection Procedure for the BBX-100A-8POS Service Disconnect:

1. Locate the service entrance panel on the enclosure (exterior). Remove the cover

to access the circuit breaker assembly. If this service panel is to be used as the
primary service entrance, neutral must be bonded to ground by installing the
green bonding screw (provided) in the hole in the neutral bus.

2. Remove the knockout located at the base of the service entrance to accept the

conduit.

3. Install the conduit nipple into the service entrance via the knockout and secure

with the appropriate threaded conduit locknut.

4. Locate the two screw terminals (L1 and L2) on the bottom of the input circuit

breaker.

5. Connect one of the incoming black #6 AWG wires to L1 (left terminal). Connect

the remaining black (or red) #6 AWG wire to L2 (right terminal). Note: if the wire
at L2 is black, mark it with red tape (or label).

6. Connect the white #6AWG wire to the neutral (N) bus lug, located to the top right

of the circuit breaker assembly.

7. Connect the #6AWG bare solid or stranded wire for the Grounding Electrode

Conductor (earth ground) to the ground and neutral bus located to the right side
of the circuit breaker assembly.

8. Notify the electrical inspector to approve the service entrance wiring. Once

approved, contact the local power utility for electrical service.

Neutral (N) Bus Lug

Line 2

Line 1

Grounding Electrode

Conductor

1

Fig. 4-1, BBX-100A-8POS Service Disconnect