4.0 Installation,

continued

4.3 Battery

Identifi cation

Each battery contains a DATE CODE. This date code must be recorded in the maintenance
log. If batteries other than those sold by Alpha are used, consult the battery manufacturers’
documentation for date code type and placement.

4.4 Battery Terminal Connections

The accompanying drawings are for illustrative purposes only. Various types of batteries
with different mounting styles and hardware may be installed with the system. ALWAYS
refer to the battery manufacturer's specifi cations for correct mounting hardware and torque
requirements. During maintenance procedures, refer to the manufacturer's specifi cations for
the maintenance torque requirements.

Mounting hardware requirements may vary with battery manufacturers. Use only the
hardware recommended by your particular battery manufacturer.

As of January 1, 2007, AlphaCell batteries will be manufactured with threaded insert
terminals. Previous AlphaCell models with fl ag terminals will no longer be available. To
facilitate this change, each AlphaCell battery is shipped with two 3/4", 1/4-20 bolts, washers,
and lock washers for terminal connections.

Fig. 4-11, Alpha Cell Battery Date Code

CAUTION!

Do not use the 1" hardware included with the Battery Cable Kit for connecting directly to the threaded
insert terminals. The threaded inserts are only 3/4" deep. Using 1" hardware will damage the battery
and void the warranty.

3/4" Bolt ONLY

Fig. 4-12, Terminal Connections